ASC5100G
Problem
The display shows
"Max. filling time
exceeded!
Carry on?"
The display shows
"External tank empty or
closed valve.
Check!"
The display shows
"Change the equipment
drier filter!
Go on?"
The display shows
"Change the vacuum pump
oil!
Go on?"
The display shows
"Error 01"
The display shows
"Error 02"
The display shows
"Error 52"
EN
Cause
Message that appears during
the filling process if the set
amount of refrigerant cannot
be filled.
Message that appears at the
start or during the filling of
the internal refrigerant con-
tainer if the set refrigerant
quantity cannot be attained.
This message appears when
you switch on the
AirConServiceCenter.
This message appears when
you switch on the
AirConServiceCenter.
Refrigerant was added
before draining was com-
pleted.
The air conditioning system
is leaking. There is still refrig-
erant in the air conditioning
system.
No USB stick was found/rec-
ognised
Troubleshooting
Remedy
Check that
AirConServiceCenter con-
nections are not blocked.
Check if the external refriger-
ant container still contains
enough refrigerant or if the
valves of the external refrig-
erant container are open.
Change the internal filter as
soon as possible (see chap-
ter "Changing the dryer filter"
on page 91).
To skip this, press ENTER for
3 seconds.
Change the vacuum pump oil
as soon as possible (see
chapter "Changing the vac-
uum pump oil" on page 96).
To skip this, press ENTER for
3 seconds.
Repeat the draining proce-
dure; do not interrupt it this
time.
Fix the leak.
Insert the USB stick.
Make sure that USB stick has
been formatted with the
FAT32 file system.