Installation / Preparation for commissioning

5.6 Shield connection

The shield connection is made via special EMC-compliant cable screw connections, in
which the cable shield can be connected internally.
Cable screw connection assembly, type A
Pos. 1 Union nut
Pos. 2 Sealing insert
Pos. 3 Contact sleeve
Pos. 5 Screw socket
30
1. Trim the shield braid / shield foil to the dimension "X".
2. Slide the union nut (1) and sealing insert / contact sleeve (2) + (3) over the
cable.
3. Bend the shield braid / shield foil by approx. 90° (4).
4. Slide the sealing insert / contact sleeve (2) + (3) up to the shield braid / shield
foil.
5. Fit the screw socket (5) on the housing.
6. Push the sealing insert / contact sleeve (2) + (3) flush into the screw socket
(5).
7. Screw the union nut (1) to the screw socket (5).