Item
PXG3.W100
Item
Automation Station (PX...)
Total size of configuration
data
BACnet objects total
BACnet objects perma-
nently displayed
Customized views
Item
BACnet objects
Trends
Schedulers
Graphic pages
Item
BACnet objects
Siemens
Building Technologies
2.5
System limits
2.5.1
XWP project
Limit
Description
10*
Max number of PXG3.W100 per XWP project
2.5.2
PXG3.W100
2.5.2.1
General
Limits
Description
—
The number of PX is not limited (only depends on BACnet objects and
the number of customized views).
Note: The specified Desigo PX.. limits must be adhered to (see Tech-
nical principles).
7 MB*
The limit is given by the available memory for the sum of all configura-
tion data (Configurationdata.tar).
2000*
Max. number of BACnet objects engineered on the PXG3.W100.
Total number of permanently displayed BACnet objects the
300
PXG3.W100 must update.
25*
Max. number of customized views (PXG3.W100 memory limit).
2.5.2.2
Customized views (CVs)
Limits
Description
100*
Max. number of BACnet objects per customized view.
10
Number of trends per customized view.
10
Number of schedulers per customized view.
5
Number of graphic pages per customized view.
2.5.2.3
Graphics pages
Limits
Description
60*
Max. number of BACnet objects per graphics page
Desigo Touch and Web
Compatibility & limitations – System limits
15 / 22
CM111029en_04
2014-08-15