System Limits; Xwp Project; Pxg3.W100; General - Siemens Desigo Touch Series Installation And Commissioning Instructions

Table of Contents

Advertisement

Item

PXG3.W100

Item
Automation Station (PX...)
Total size of configuration
data
BACnet objects total
BACnet objects perma-
nently displayed
Customized views
Item
BACnet objects
Trends
Schedulers
Graphic pages
Item
BACnet objects
Siemens
Building Technologies
2.5

System limits

2.5.1

XWP project

Limit
Description
10*
Max number of PXG3.W100 per XWP project
2.5.2
PXG3.W100
2.5.2.1

General

Limits
Description
The number of PX is not limited (only depends on BACnet objects and
the number of customized views).
Note: The specified Desigo PX.. limits must be adhered to (see Tech-
nical principles).
7 MB*
The limit is given by the available memory for the sum of all configura-
tion data (Configurationdata.tar).
2000*
Max. number of BACnet objects engineered on the PXG3.W100.
Total number of permanently displayed BACnet objects the
300
PXG3.W100 must update.
25*
Max. number of customized views (PXG3.W100 memory limit).
2.5.2.2

Customized views (CVs)

Limits
Description
100*
Max. number of BACnet objects per customized view.
10
Number of trends per customized view.
10
Number of schedulers per customized view.
5
Number of graphic pages per customized view.
2.5.2.3

Graphics pages

Limits
Description
60*
Max. number of BACnet objects per graphics page
Desigo Touch and Web
Compatibility & limitations – System limits
15 / 22
CM111029en_04
2014-08-15