Test 6 - Inducer On - No Ignition; Test 6 - A.O. Smith Master-Fit 100 Series Service Handbook

Commercial gas water heaters
Table of Contents

Advertisement

TEST 6

INDUCER ON
CONDITIONS:
Power On.
Plugs in Receptacles.
Inducer operating.
No power to Hot Surface Igniter (HSI)
Note LED flash code.
TEST 6
IF.........
Ignition board receptacles E1, Pin
7 to ground shows no voltage.
E1, Pin 7 has 24 Volt to ground
Voltage check of each blower
switch terminal to ground shows
voltage to only 1 terminal.
NATURAL GAS ONLY
24V is present from each switch
terminal to ground.
Voltage check to each terminal
of low gas pressure switch and
ground shows only voltage on 1
terminal
Voltage is present to each
pressure switch terminal and
ground
NO IGNITION
24 VAC Check of Blower Prover/Low Gas Pressure Circuit
THEN............
Replace ignition board.
Check wire connection to and from inducer.
Switch is open - check for proper draft (should also see LED 3 flash
code). Check for blocked exhaust. Check that blower outlet exhaust
damper is open. Replace blower (draft) proving switch.
Check wiring from blower switch to low gas pressure switch.
Switch is open - test for a minimum of 5.2 ± " W.C. Natural Gas or
10.5" Propane, flowing supply gas pressure (should also see 3 Flash
LED code). Replace low gas pressure switch.
Check wiring from low gas pressure switch to ignition board
receptacles E1, Pin 10.
Servicing should only be performed by a Qualified Service Technician
27