7. Technical data

7. Technical data
Motor operator, control circuit
Rated operational voltage U [V]
Operating voltage range
Operating angle
Operating time
Protection degree
Rated impulse withstand voltage U
Voltage supply
F2
Cable of the push-buttons (no SELV)
Maximum cable length
State information of locking (no SELV)
Handle attached or motor operator locked
Locking motor operator
Operating temperature
Transportation and storage temperature
Altitude
Table 7.1
General technical data of motor operators
Value
220-240 Vac 50-60 Hz
110-125 Vac/dc 50-60 Hz
48 Vdc
24 Vdc
0.85... 1.1 x U
90° 0-I, I-0, 0-II, II-0; 180° I-0-II
See the Table 7.2
IP 20, front panel
4 kV
imp
PE N L
Max. MCB 16 A
C II I 0
100 m
11-12-14 (C/O)
23-24 (NO)
-25... +55 °C
-40... +70 °C
Max. 2000 m
Installation and operating instructions, OTM_C
1SCC303002M0204, rev. D
Cabling
1,5 -2,5 mm
2
1,5 -2,5 mm
2
1,5 -2,5 mm
2
1,5 -2,5 mm
2
25