# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.
11.2.9.25
Setpoint: #SlowStopDel
Group
Pwr Management
Range [units]
0 .. 600 [s]
Related FW
standard v3.1.0
Description
This setpoint is used to adjust how long the particular gen-set will suppress
it's own Slow stop alarm to give chance to another gen-set to start and
replace the defective one.
If there isn't any available gen-set to start, the alarm is not suppressed.
N
:
OTE
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.
11.2.9.26
Setpoint: #MinRunPower 1
Group
Power Management
Range [units]
0 .. 65000 [kW]
Related FW
standard v3.1.0
Description
This setpoint is used to adjust certain minimum value of the sum of nominal
power of all running gen-sets. If the function is active, then the gen-sets
would not be stopped, although the reserve for stop is fulfiled, if the total
remaining nominal power dropped below this minimal value.
There are 3 different MinRunPower setpoints, this particular one is activated
by the input MinRun power 1 which is in MINT application (in InteliMains it is
for compatibility purposes only).
N
:
OTE
When more than one binary input MinRunPower is activated then
MinRunPower with the highest number is active.
N
:
OTE
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.
NT
InteliMains
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp – April 2015
243