11.2.1.14
Setpoint: PeakAutS/S del
Group
Process control
Range [units]
OFF, 1 .. 3200 [s]
Related FW
standard v3.1.0
Force value
YES
possible
Description
The setpoints adjusts the delay for automatic Peak start/stop function. Set 0
(OFF) to disable Peak automatic start function. See also the setpoints
PeakLevelStart
N
:
OTE
The delay for this function is counted down in any mode if the conditions are
fulfilled (i.e. in OFF when the Mains Import in kW is higher than
PeakLevelStart).
11.2.1.15
Setpoint: Peak kVA Start
Group
Process control
Range [units]
Peak kVA Stop
Related FW
standard v3.1.0
Force value
YES
possible
Description
If the object apparent consumption
the power of 2) exceeds this setpoint for time longer than
the gen-set starts automatically (in SPtM application) or group of gen-sets is
started by InteliMains. Adjusting the
autostart. See also the setpoint
NT
InteliMains
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp – April 2015
and PeakLevelStop.
.. 32000 [kVA]
(Object P
PeakKVAS/S del
Peak kVA
to the power of 2 +
Object Q
PeakKVAS/S
to 0 (OFF) disables the
Stop.
to
del,
162