Summary of Contents for CellarCool 3500 Evaporator
Page 1
WALL-MOUNTED & FULLY DUCTED VERSION 4 TECHNICIAN’S MANUAL 24V Thermostat Conversion Kit Option NOTICE: To activate the split system warranty, the installing certified HVAC/R service tech must complete the split system warranty checklist and send back to CellarCool.
Page 2
CellarCool. Every effort has been made to ensure that the information in this manual is accurate. CellarCool is not responsible for printing or clerical errors.
INTRODUCTION Customer Service Thank you for purchasing a CellarCool cooling system. We strive to provide the highest-quality products and the best possible customer service. If you have any questions about your system, please call us at 1-800-343-9463 or visit cellarcool.com.
CellarCool units utilize a solenoid valve on the liquid line and a low-pressure switch on the suction line. When the thermostat calls for cooling, the solenoid valve opens, permitting the flow of refrigerant. The low-pressure switch then signals the compressor to cycle on.
7. CellarCool requires that all split systems be installed by a certified HVAC-R technician only. NATE or equivalent is recommended. If you encounter a problem with your CellarCool system, please refer to the Troubleshooting Guide. If you have any further questions or concerns, or need assistance, please contact CellarCool’s Customer Service at 1-800-343-9463.
Allow the condensing unit to sit for 24 hours prior to start-up. The condensing unit can be placed in the installation location, piped, and evacuated during this time. NOTE: CellarCool units are manufactured in the USA and tested prior to shipment. •...
QUICK REFERENCE GUIDE Front / Side View Evaporator unit Filter grille Rear / Side View Mounting keyholes (4) THROUGH THE WALL Option 1 Knockout for wiring Line set knockout Knockout for drain line Thermostat wire routing for optional 24-volt thermostat (NOT INCLUDED) INSIDE CELLAR Option 2...
Can maintain a 55°F temperature differential with up to 110°F condenser air intake temperature Warranty Two-year limited warranty (parts and labor) *Each cellar is unique and has specific cooling requirements. Heat load calculations should always be performed prior to selecting a cooling unit. www.cellarcool.com | Page 7...
Can maintain a 55°F temperature differential with up to 110°F condenser air intake temperature Warranty Two-year limited warranty (parts and labor) *Each cellar is unique and has specific cooling requirements. Heat load calculations should always be performed prior to selecting a cooling unit. www.cellarcool.com | Page 9...
Supply air Return air Duct plenum FULLY DUCTED UNIT SPECIFICATIONS 5000 Evaporator 5000 Condenser Model (Fan Coil Unit) (Air-Cooled Condensing Unit) Cellar Size Approx. 1750 cu. ft., provided cellar is fully insulated and sealed with proper vapor barrier* BTU/h w/85°F air 3788 entering condenser coil Dimensions...
Page 13
NOTE: Cool temp may indicate liquid in the compressor. Voltage and Amp Draw A. Measure voltage to compressor and amp draw. Condensation Drain Test A. Pour water into the drain pan to assure it drains properly. www.cellarcool.com | Page 11...
24V THERMOSTAT CONVERSION KIT WIRING INSTRUCTIONS The 24V Thermostat Conversion Kit requires a standard 18-5 thermostat wire to be run from the evaporator unit to the thermostat. The white wire will not be used, as there is no heating function. (Some thermostats need a common wire and some do not;...
For ease of installation, remove the nine (9) screws Relief securing the top and remove the top. Install strain relief around thermostat wires if routed through the circular connector hole in the bottom corner (see illustration). Unit Panel www.cellarcool.com | Page 13...
INSTALLING THE WALL-MOUNTED EVAPORATOR UNIT Refer to the Wall-Mounted Evaporator Unit Installation Template for more information about mounting the wall-mounted evaporator unit. 1. Locate two (2) wall studs in the desired mounting location spaced 16” on center. 2. Mark vertical lines on each stud 16” apart. 3.
Page 17
17. Connect the green wire to the green wire, the black wire to the black wire, and the white wire to the white wire. 18. Install the supplied black strain relief to secure the power wires in the housing. 19. Secure all wiring neatly and as close to the left wall as possible in order to minimize airflow obstruction. www.cellarcool.com | Page 15...
DRAIN LINE Condensation Drain Line (not provided, but required) The condensation drain line tube moves excess condensation from the evaporator unit to a proper discharge location. It is important for the drain line tube to be properly connected in order to prevent leakage and other problems associ- ated with excess condensation.
Install strain relief around thermostat wires if routed through the circular connector hole in the bottom corner of the housing. Drain line Thermostat Wire Strain Relief Unit Panel Thermostat wire routing for optional 24V thermostat conversion kit (THERMOSTAT NOT INCLUDED) www.cellarcool.com | Page 17...
Page 20
INSTALLING THE FULLY DUCTED EVAPORATOR 1. Using 1/4” and 1/2” copper tubing, route the liquid and suction lines through the knockouts in the housing. Be sure to extend the tubing far enough outside of the housing to extend through the wall if necessary. NOTE: 1/2” copper tubing will slip over the 3/8”...
Connect the yellow wire to the purple #12 wire, and connect the blue wire to the grey #13 wire. Blue Black 115V Line White 115V Neutral Green Ground Green Green White Black White White FV-30VQ3 www.cellarcool.com | Page 19...
WM & FD SERIES COPELAND COLD WEATHER START KIT WIRING DIAGRAM For systems manufactured after October 31, 2018 Black Black COPELAND CWSK HEATER www.cellarcool.com | Page 21...
Provide a weatherproof disconnect for the condensing unit if it is located outside. Power surges and spikes can damage sensitive electrical equipment. CellarCool recommends plugging the unit into a surge protector or power conditioner in order to protect your system. As outlined in our terms and conditions, power surges and spikes are not covered under warranty.
(3) feet of horizontal clearance in every direction around the unit (five feet is ideal). The unit should be elevated 18 inches in order to avoid any possible flooding or damage by animals, and should be clear of leaves, dirt, and other debris. www.cellarcool.com | Page 23...
Page 26
WM/FD SERIES WIRING PROCEDURES 1. Locate or install an electrical outlet near the condensing unit. 2. Follow the instructions listed below to wire the condensing unit. 3. Leave the circuit breaker off until the unit is ready to charge. NOTE: Do not apply power to a system without refrigerant. Copeland Wiring Procedure Step # Use a ¼”...
Page 27
WM & FD SERIES Copeland Wiring Procedure Step # Remove the cover to expose the internal wires. Copeland Wiring Procedure Step # Route the required 115V power wires into the open clamp on the enclosure. www.cellarcool.com | Page 25...
Page 28
Copeland Wiring Procedure Step # Tighten the screws on the clamp to secure wire casing or conduit in place. Copeland Wiring Procedure Step # Perform the following wire connections: • Insert the Line 115V wire into the “H” lever connector •...
Page 29
WM & FD SERIES Copeland Wiring Procedure Step # Push wires back into enclosure. Copeland Wiring Procedure Step # Re-install cover. www.cellarcool.com | Page 27...
LINE SET PIPING DIAGRAMS It is required to size the suction line tubing according to this chart. Line Set Length <25ft 26-50ft 50-100ft WM/FD 3500/5000 Vertical Rise 15ft <3ft 3-10ft >10ft <3ft 3-10ft >10ft Horizontal Tubing 1/2” 5/8” Suction Line Vertical Rise 1/2”...
Page 31
• After confirming that there is fresh oil in the vacuum pump, connect the 3/8” hose from the manifold to the pump. • Start the pump and run it until the micron gauge on the evaporator unit reads 500 microns or less. • Disconnect the vacuum pump from the system. www.cellarcool.com | Page 29...
Page 32
INSTALLING THE CONDENSING UNIT (continued) • Break the vacuum by pressurizing the system to approximately 5 PSI with R-134a refrigerant. • Remove the micron gauge from the access valve. Charging • With the power off to the condensing unit, admit liquid refrigerant through the liquid line service valve until the refrigerant stops flowing.
NOTE: Max ducting length is 25 feet. NOTE: A 12”x12” return air filter grille must be installed to prevent contaminants from entering the cooling system. Supply duct must be insulated so it does not sweat or pick up heat. www.cellarcool.com | Page 31...
SYSTEM OPERATION The cooling system is equipped with the hardware needed to support a 24-volt air conditioning thermostat (not included). Initial Start-Up Set the thermostat to COOL and fan switch to AUTO. Lower The condensing unit controller is preset at the factory. The the setpoint to the desired cellar temperature.
2. Check wiring connections and integrity of cords 3. Pour a 50/50 bleach solution into the drain line every spring *CellarCool recommends filters with a mean efficiency reporting value (MERV) of 4 or better. Filters are not included with the unit.
Page 36
Emerson Electronic Unit Controller ™ Quick setup and troubleshooting guide Fan light 1 & 2 Compressor Adjusting Low Pressure Settings Book of Alarms – (Fan cycle units only) to enter alarm menu Hold DOWN and SET simultaneously for 3 seconds to enter menu (PSI light will ...
CELLARCOOL TROUBLESHOOTING GUIDE Unit has ice forming on the evaporator unit Possible cause Solution Evaporator filter or coil is dirty Remove the filter and wash it, then clean the coil with a vacuum. If coil is very dirty, use a spray bottle with a small amount of liquid dish detergent or coil cleaner.
Page 39
Please contact the installing technician to troubleshoot Compressor and /or starting components faulty Please contact the installing technician to troubleshoot Humidity in cellar too low Possible cause Solution Not enough moisture Purchase and place a humidifier (or a decorative fountain) in cellar www.cellarcool.com | Page 37...
Page 40
Units equipped with the 24V Thermostat Conversion Kit: Unit does not power up/run Possible cause Solution Batteries on thermostat have lost their charge Change batteries Thermostat wired incorrectly Check wiring on 24V thermostat and correct Wiring issue at evaporator unit Contact Customer Service for troubleshooting 24V transformer in evaporator unit has failed Contact Customer Service for troubleshooting...
Page 41
2. Check wiring connections and integrity of cords 3. Pour a 50/50 bleach solution into the drain line every spring *CellarCool recommends filters with a mean efficiency reporting value (MERV) of 4 or better. Filters are not included with the unit.
Page 42
AE5-1340 October 2006 Care and Cleaning of Air Cooled Condensing Units Introduction Proper care is essential to assure good life of condensing Coil cleaning agents must not be allowed to drain into units. Dirty or damaged condensers will reduce the the condensate pan as this may cause damage.
WM & FD SERIES BYPASS TEST PROCEDURE NOTE: If instructed by a CellarCool representative, follow the directions below to test the cooling unit using the bypass plug provided in the accessory kit. 1. Disconnect power from the evaporator unit. 2. Loosen the two (2) screws on the front of the grille or duct plenum.
TECHNICAL ASSISTANCE CellarCool Customer Service is available Monday through Friday from 6:00 a.m. to 4:00 p.m. Pacific Standard Time. The appointed customer service representative will be able to assist you with your questions and warranty information more effectively if you provide them with the following: •...
CellarCool warrants against defects in material and workmanship as follows: 1. LABOR - For a period of two (2) years commencing on the date of purchase, CellarCool will, at its option and discretion, reimburse up to $250 to the End User for cost incurred for servicing, repairing, removing or installing warranty parts.
Page 46
8. This limited warranty is voided if installed in an enclosure of insufficient design that does not follow the Product installation requirements stated herein and in the owner’s manual. 9. Removing the rivets from the Product’s unit housing without prior authorization from CellarCool voids this limited warranty.
Page 47
E. End User is responsible for all costs incurred for the installation and/or removal of the Product, or any part thereof, unless such cost has been agreed by CellarCool to be a warranty repair prior to the work being performed.
Page 48
Conditions of Sale shall be interpreted as through drafted jointly by CellarCool and Purchaser. Any dispute will be resolved by the courts in and for the County of San Joaquin, State of California, and all parties, CellarCool, Purchaser and End User, hereby irrevocably submit to the personal jurisdiction of such courts for that purpose.
Page 49
Web: www.cellarcool.com B. Technical Assistance. CellarCool Customer Service is available Monday through Friday from 6:30 a.m. to 4:00 p.m. PST. The Customer Service representative will be able to assist you with your questions and warranty information more effectively if you provide them with the following: 1.
Page 50
CellarCool 1738 E. Alpine Ave Stockton, CA 95205 1(800) 343-9463 www.cellarcool.com...
Need help?
Do you have a question about the 3500 Evaporator and is the answer not in the manual?
Questions and answers