Reference manual
00809-0500-4750
Table C-2: Device specific parameters
TB Index
Parameter Name
104
INT_SIM_REF_VALUE
105
INT_SIM_VALUE
106
METER_VERIF_EP_LIM
107
METER_VERIF_FLOWING_LIM
108
METER_VERIF_NO_FLOW_LIM
109
RECALL_FINGERPRINT_VALUES
110
PERFORM_REFINGERPRINT_FLO
WTUBE
111
PERFORM_METER_VERIFY
112
FINGERPRINT_SELECT
113
COIL_CURRENT_VALUE
114
37HZ_AUTOZERO_OFFSET
115
SERIAL_NUMBER
Block/transducer errors
The BLOCK_ERR conditions are listed in the table below. The XD_ERROR conditions are
listed in
Table C-3: BLOCK_ERR conditions
Condition number
3
6
7
13
14
Reference manual
(continued)
Description
Internal Flow Simulator Reference Value.
The internal flow simulator reading.
Flowmeter Verification Limit – Empty Pipe condition.
Flowmeter Verification Limit – Flowing condition.
Flowmeter Verification Limit – No Flow condition.
Perform a recall of the previous fingerprint values.
Perform the re-fingerprint command.
Note
The parameter FINGERPRINT_SELECT needs to be configured before
the Refingerprint operation is started.
Perform the meter verification command.
Note
The parameter METER_VERIF_TEST_SCOPE and
METER_VERIF_TEST_COND_IN needs to be configured before the
Refingerprint operation is started.
Components to re-fingerprint.
Note
This parameter needs to be configured before the Refingerprint
operation is started via the PERFORM_REFINGERPRINT_FLOWTUBE
parameter.
Coil Current Value: Coil current measurement.
37Hz Auto Zero Offset: Auto Zero Offset at 37.5 Hz
This parameter reads directly from Resource Block parameter
OUTPUT_BOARD_SN.
Table
C-3.
Condition name and description
Simulate active
Device needs maintenance soon
Input failure/process varialbe has bad status
Device needs maintenance now
Power up: the device was just powered up
Transducer block
May 2019
171