RACK MOUNT POWER STRIPS AND SURGE SUPPRESSORS
SP197A (48" Vertical Surge Suppressor Strip), SP198A (70" Vertical Surge
Suppressor Strip), and SP199A (77" Vertical Surge Suppressor Strip):
Compliance —
Power —
Rated Current —
Protection —
Indicator —
Input —
Outlets —
Size —
Weight —
10
FCC Class A, DOC Class/MDC classe A, UL listed,
CSA certified
120 VAC
15 amps (has front-mounted resettable breaker)
Surge suppression:
Type: Single-stage;
UL 1449 clamping category: 330 volts peak
transient voltage;
Actual clamp voltage: 312 volts peak;
Maximum surge-energy resistance: 13,000 amps;
EMI/RFI resistance: Up to 40 dB
(1) Front-mounted Protection LED (goes dark when
unit's protection circuitry has absorbed surge and
been destroyed)
(1) 6-ft. (1.8-m) 14/3 (14-AWG, 3-conductor) cord
with NEMA 5-15P plug
SP197A: (10) Front-mounted NEMA 5-15Rs;
SP198A: (11) Front-mounted NEMA 5-15Rs;
SP199A: (12) Front-mounted NEMA 5-15Rs
SP197A: 48"L x 1.5"W x 1.2"D (121.9 x 3.8 x 3.1 cm);
SP198A: 70"L x 1.5"W x 1.2"D (177.8 x 3.8 x 3.1 cm);
SP199A: 77"L x 1.5"W x 1.2"D (195.6 x 3.8 x 3.1 cm)
SP197A: 3.46 lb. (1.57 kg);
SP198A: 4.42 lb. (2.00 kg);
SP199A: 4.96 lb. (2.25 kg)