Daikin FXSQ05TAVJU Engineering Data page 8

Msp concealed ducted unit
Hide thumbs Also See for FXSQ05TAVJU:
Table of Contents

Advertisement

Specifications
MSP Concealed Ducted Unit
Model
Power supply
1
3 Cooling capacity
2
3 Heating capacity
Casing / Color
Dimensions: (H×W×D)
Rows×Stages×FPI
Coil (Cross
fin coil)
Face area
Model
Type
Motor output
Fan
Airflow rate (H/M/L)
External static
pressure
Drive
Temperature control
Sound absorbing thermal insulation material
Liquid pipes
Gas pipes
Piping
connections
Drain pipe
Weight
6 Sound pressure levels (H/M/L)
6 Sound power level
Safety devices
Refrigerant control
Connectable outdoor unit
Standard accessories
Specification
Drawing No.
Sound level
Notes:
1. Nominal cooling capacities are based on the following conditions:
Return air temperature: 80.0°FDB (26.7°CDB), 67.0°FWB (19.4°CWB)
Outdoor temperature: 95.0°FDB (35.0°CDB)
Equivalent refrigerant piping length: 25 ft (7.6 m) (Horizontal)
2. Nominal heating capacities are based on the following conditions:
Return air temperature: 70.0°FDB (21.1°CDB).
Outdoor temperature: 47.0°FDB (8.3°CDB), 43.0°FWB (6.1°CWB)
Equivalent refrigerant piping length: 25 ft (7.6 m) (Horizontal)
3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4. External static pressure is changeable in 13 stages (05~15 type), 11 stages (18~48 type), 10 stages (54 type)
within the ( ) range by remote controller.
5. Air filter is not standard accessory, but please mount it in the duct system of the suction side.
Select its dust collection efficiency (gravity method) 50% or more.
6. Anechoic chamber conversion value, measured under JIS conditions. During actual operation,
these values may be higher as a result of installation conditions.
7. Refer to Electric Characteristics for the power input.
6
FXSQ24TAVJU
1 phase, 60 Hz, 208/230 V
Btu/h
24,000 (7.0)
(kW)
Btu/h
27,000 (7.9)
(kW)
Galvanized steel plate
9-11/16 × 39-3/8 × 31-1/2
in. (mm)
(245 × 1,000 × 800)
2×26×19
ft² (m²)
3.10 (0.288)
Sirocco fan
W
cfm
742/618/512
(m³/min)
(21/17.5/14.5)
in. H
O
Standard 0.20 (0.60-0.20
2
(Pa)
(50 (150-50))
Direct drive
Microprocessor thermostat for cooling and
heating
φ3/8 (φ9.5) (Flare connection)
in. (mm)
φ5/8 (φ15.9) (Flare connection)
in. (mm)
in. (mm)
External dia. 1-1/4 (32)
(
Internal dia. 1 (25)
lbs (kg)
77 (35)
dB(A)
36.0/32.0/29.0
dB(A)
Fuse, Fan driver overload protector
Electronic expansion valve
R410A VRV series
Operation manual, Installation manual,
Drain hose, Sealing material, Clamps,
Washers, Screws, Insulation for fitting,
Clamp metal, Air discharge flange,
Air suction flange, Conduit mounting plate
C: 3D110282
C: 4D110416
230
4)
5
VP25
)
64
EDUS391777-F17
FXSQ30TAVJU
1 phase, 60 Hz, 208/230 V
30,000 (8.8)
34,000 (10.0)
Galvanized steel plate
9-11/16 × 39-3/8 × 31-1/2
(245 × 1,000 × 800)
3×26×19
3.10 (0.288)
Sirocco fan
230
812/689/565
(23/19.5/16)
Standard 0.20 (0.60-0.20
(50 (150-50))
Direct drive
Microprocessor thermostat for cooling and
heating
5
φ3/8 (φ9.5) (Flare connection)
φ5/8 (φ15.9) (Flare connection)
VP25
External dia. 1-1/4 (32)
(
Internal dia. 1 (25)
82 (37)
37.5/34.0/30.0
65.5
Fuse, Fan driver overload protector
Electronic expansion valve
R410A VRV series
Operation manual, Installation manual,
Drain hose, Sealing material, Clamps,
Washers, Screws, Insulation for fitting,
Clamp metal, Air discharge flange,
Air suction flange, Conduit mounting plate
C: 3D110282
C: 4D110417
FXSQ-TAVJU
4)
)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents