Mitsubishi Electric CITY MULTI CMH-WM-V-A Series Data Book page 4

Air conditioning systems
Table of Contents

Advertisement

1. SPECIFICATIONS
Model name
Power source
Power input
Cooling
(220/230/240) Heating
Current input
Cooling
(220/230/240) Heating
Sound pressure level (measured in anechoice room)
Applicable temperature range of installation site
External finish
Connectable outdoor/heat source unit capacity
External dimension H x W x D
Refrigerant piping
To outdoor/heat source unit
diameter
Liquid pipe
Gas pipe
Water piping
To Indoor unit
diameter
Inlet Pipe
Outlet Pipe
Net weight
Standard
Document
attachment
Accessories
Optional parts
Note
1.Works not included:
Installation/foundation work, electrical connection work, duct work, insulation work, power source switch, and other items are not specified in this specifications.
2.The equipment is for R32 refrigerant.
3.Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors.
(For use in quiet environments with low background noise, position the Hydro unit at least 5 m away from any indoor units.)
4.Please install the Hydro unit in a place where noise will not be an issue.
5.Please attach an expansion vessel (field supply).
6.Use copper, plastic, steel, or stainless steel pipes for the water circuit. Furthermore, when using copper pipe-work use a non-oxidative brazing method.
Oxidation of the pipe-work will reduce the pump life.
7.When brazing the pipes, be sure to braze, after covering a wet cloth to the insulation pipes of the units in order to prevent it from burning and shrinking by heat.
8.Please install an air purge valve where air will gather in the water circuit.
9.Please install a pressure reducing valve and a strainer on the water supply to the Hydro unit.
10.Please refer to the databook or the installation manual for the specified water quality.
11.Please always make water circulate or pull out the circulation water completely when not using it. *Please do not use it as a drinking water.
12.Please do not use ground water and well water.
13.When installing the Hydro unit in an environment which may drop below 0 °C, please add antifreeze to the circulating water.
(Refer to the data-book and the installation manual).
14.R32 is flammable, and certain restrictions apply to the installation of units.
When installing new units, moving the existing units, or changing the layout of the room,
ensure that installation restrictions are observed.
For detail, refer to the section in the Databook on installation restrictions.
15.Drain or condensation water will be discharged from hydro units during test run. If this will be a problem, install a separately sold drain pan.
16.Do not install the unit where it could be salt-damaged.
MEES18K070
50 Hz
kW
0.90/0.90/0.90
kW
0.90/0.90/0.90
A
4.69/4.48/4.30
A
4.69/4.48/4.30
dB <A>
°C (D.B.)
(Lower part drain pan: Pre-coated galvanized sheets + powder coating)
mm
in.
M300
mm (in.)
9.52 (3/8)
O.D.
Brazed
mm (in.)
22.2 (7/8)
O.D.
Brazed
mm (in.)
I.D.
mm (in.)
I.D.
kg (lbs)
CMH-WM350V-A
1-phase 220-230-240 V
60
-5~52
Pre-coated galvanized steel sheets
(E)M300~350
660 x 920 x 740
25-63/64 x 36-7/32 x 29-9/64
Connectable outdoor/heat source unit capacity
M350
EM300
12.7 (1/2)
9.52 (3/8)
Brazed
Brazed
28.58 (1-1/8)
28.58 (1-1/8)
Brazed
Brazed
40 (1-1/2) housing joint
40 (1-1/2) housing joint
122 (269) [126 (278) with water]
Y-type strainer, Auto air vent valve, Joint, Elbow, Pipe
Drain pan (PAC-SH01DP-E)
Hydro unit
60 Hz
0.90/0.90/0.90
0.90/0.90/0.90
4.69/4.48/4.30
4.69/4.48/4.30
EM350
12.7 (1/2)
Brazed
28.58 (1-1/8)
Brazed
3