Autotest Procedure In Accordance With Standard Cei 0-21; Running The Tests From The Display Menu - ABB UNO-2.0-TL-OUTD Product Manual

Solar inverters from 2.0 to 4.2 kw
Hide thumbs Also See for UNO-2.0-TL-OUTD:
Table of Contents

Advertisement

A
UTOTEST procedure in accordance with standard CEI 0-21
R
unning the tests from the display menu
Settings
ENTER
Password 0000
ENTER
Autotest
ENTER
U>>
U<<
F>>
F<<
U>(10min)
U>
U<
F>
F<
The autotest according to the grid standard CEI-021 can be launched via
the menu on the display.
The conditions required to perform an Autotest are:
• The grid standard must be set to CEI-021.
• You must not intervene in any way while the test is underway
• You must check that the equipment has a stable network connection.
In the Autotest section of the SETTINGS menu, select the type of test the
equipment is to run from the following:
OV Test – parameters:
U>>; U>; U> (10Min)
Disconnection from the distribution grid due to "Over-voltage"
UV Test – parameters:
U<<; U<
Disconnection from the distribution grid due to "Under-voltage"
OF Test – parameters:
F>> and F>
Disconnection from the distribution grid due to "Over-frequency"
UF Test – parameters:
F<< and F<
Disconnection from the distribution grid due to "Under-frequency"
Go to the SETTINGS > Autotest menu
If one of the protections is disabled (from the Service menu), N/A (not
applicable) will appear next to the name of the test.
While one of the tests is being performed, the set limits will be gradually
increased/reduced (depending on the type of test) until the threshold at
which the inverter is disconnected from the grid is reached. The procedu-
res for running the Autotest comply with the legislation in force.
The display shows the message "Performing Test" when the test has
started.
- 102 -