Description of the device

2.6 SET button

2.6
SET button
With a SCALANCE S615, the SET button is on the front of the housing.
The SET button has the following functions:
● Restart
Hold down the button for shorter than 3 seconds to run a restart.
● Loading new firmware
If the normal procedure with the "Load & Save" menu of Web Based Management does
not work, the SET button can be used to load new firmware. This situation can occur if
there is a power outage during the normal firmware update.
– Hold down the button until the red fault LED (F) starts to flash after approximately 3
– Now release the button. The bootloader waits in this status for a new firmware file that
You will find more information in the section "Service and Maintenance" in the
SCALANCE S615 Web Based Management configuration manual.
22
seconds.
you can download using TFTP.