Lp Conversion - Trane Oxbox 14 Seer Series Installation Instructions Manual

Package gas electric units
Table of Contents

Advertisement

Table 4-1: Natural gas pipe capacity table
(CFH - Cubic Feet of Gas Per Hour)
Equivalent length of pipe (ft.)
Nominal iron
pipe size (in.)
10
20
1/2
132
92
3/4
278
190
1
520
350
1-1/4
1050
730
1-1/2
1600
1100
After determining the pipe length, select the pipe size which will
provide the minimum cubic feet per hour required for the gas input
rating of the furnace. By formula:
Furnace input (BTU/HR)
CFH=
Heating Value of Gas (BTU/Cubic Foot)
The gas input of the furnace is marked on the furnace rating plate.
The heating value of the gas (BTU/Cubic FT) may be determined by
consulting the local natural gas utility or the L.P. gas supplier.
Table 4-2: LP gas pipe capacity table (CFH - Cubic Feet of Gas Per Hour)
Nominal iron
pipe size (in.)
10
1/2
275
3/4
567
1
1071
1-1/4
2205
1-1/2
3307
2
6221
Example (LP): Input BTU requirement of unit, 150000
Equivalent length of pipe, 60 ft. =3/4" IPS r
Temperature sensor
Igniter
Burner Box
Burner
30
40
50
60
70
73
63
56
50
46
152
130
115
105
96
285
245
215
195
180
590
500
440
400
370
890
760
670
610
560
20
30
40
189
152
129
114
393
315
267
237
732
590
504
448
1496
1212
1039
913
2299
1858
1559
1417
4331
3465
2992
2646
Flame sensor
Orifice
Fig. 4-2 Burner and Gas Valve Arrangement

4.2 LP CONVERSION

This unit is equipped at the factory for use on Natural Gas only.
80
Conversion to LP Gas requires a special kit which is included with
43
the unit. DO NOT BURN ANY LIQUID FUEL OR SOLID FUEL IN
THIS UNIT. Burning any unapproved fuel will result in damage to
90
this unit heat exchanger, which could result in fire, Carbon
170
Monoxide poisoning, explosion, personal injury,
damage or death.
350
530
Convert the valve to use liquefied petroleum (LP) gas by replacing the
pressure regulator spring with the conversion kit spring. This LP kit
spring allows the regulator to maintain the proper manifold pressure
for LP gas. The correct burner LP orifices are included in the kit.
NOTE: The LP conversion kit is included with the unit. See
Conversion Kit Index shipped with unit for proper LP kit number.
Furnace conversion to LP gas must be performed by a qualified
technician.
Equivalent length of pipe (ft.)
50
60
70
80
103
96
89
217
196
182
409
378
346
834
771
724
1275
1181
1086
2394
2205
2047
WARNING
90
100
125
150
83
78
69
173
162
146
132
322
307
275
252
677
630
567
511
1023
976
866
787
1921
1811
1606
1496
on/off Lever
Gas Valve
Inlet
Gas Manifold
installation & owner's manual
property
63
17

Hide quick links: