CONTENTS Cleaning the filter ball valve 31 SPECIAL INFORMATION Replacing the anode 31 INSTALLATION Checking the diaphragm expansion vessels 32 General information �����������������������������������������3 Specification ������������������������������������������������ 33 Relevant documents 3 10.1 Dimensions and connections 33 Information on the appliance 3 10.2 Connection examples 34 Standardised output data 3...
SPECiaL iNfOrmaTiON | i NSTaLLaTiON General information SPECiaL iNfOrmaTiON iNSTaLLaTiON - Observe all applicable national and regional re- General information gulations and instructions during installation. These instructions are intended for qualified contractors. - The appliance is not approved for outdoor installation. Relevant documents - Observe the requirements concerning the ins- 336513 Operation...
iNSTaLLaTiON Safety Operation of the appliance in buildings with Depending on the chosen test method and the extent to which this method differs from the test conditions defined in the first combustion equipment paragraph of this section, any deviations can be considerable. If the building contains combustion equipment (tiled stoves, fi- Additional factors that have an influence on the test values are replaces, etc.), approval must be obtained from the responsible...
iNSTaLLaTiON appliance description As the appliance can produce negative pressure in the installa- - Installation instructions tion room, we recommend using a tightly sealing door between - Notification list the installation room and the living space containing combustion - Transport aid, comprising two angled brackets with screws equipment.
Page 6
iNSTaLLaTiON appliance description The cross-countercurrent heat exchanger ensures that up to 90 % - Area cooling means: underfloor heating systems, wall hea- of the heat in the extract air is returned with the supply air into ting systems and generally all heating systems that have no the living space.
iNSTaLLaTiON Preparation 3.4.3 Frost protection for the cross-countercurrent heat The room in which the appliance is to be installed must meet the exchanger following conditions: - The room must be free from the risk of frost. A heat exchanger in the path of the outdoor air flow preheats the outdoor air, and thus prevents the cross-countercurrent heat - The floor must have sufficient load bearing capacity.
iNSTaLLaTiON Preparation Outdoor/exhaust air connection with air hose Outdoor air mechanical ventilation connection option ≥500 ≥300 1 Filter box Air routing Prevent air stream „short circuits“. The air intake and discharge apertures in the external walls should be arranged around cor- ners.
Page 9
iNSTaLLaTiON Preparation The floor between the installation room and living areas must Anti-vibration separation have carefully applied anti-vibration separation. Ensure that no With the anti-vibration feet, it is possible to install the appliance pipes are routed on or in the wall and that the air ducts have on floating screed, as long as this has been applied correctly.
iNSTaLLaTiON Preparation Electrical installation Transport Permission must be obtained from your local power supply utility. Material losses If the appliance is transported without packing and wit- WARNING Electrocution hout using a pallet, its outer casing may be damaged. Carry out all electrical connection and installation work Remove the side panels and doors in such cases.
iNSTaLLaTiON installation Installation Siting the function module Material losses Never tilt the appliance excessively. Contacts between the casing and the floor can damage the paintwork. 1 Fixing screw on the r.h. side panel f At the top of the gap between door and appliance, undo the fixing screw for the r.h.
Page 12
iNSTaLLaTiON installation Outdoor air mechanical ventilation connection option f Press the core piece inward, carefully break it out and remo- ve it. Note f Smooth out the line of breakage. Observe the minimum clearance at the back of the ap- f Clean the aperture.
iNSTaLLaTiON installation Installing the cylinder module f Undo the screws underneath the pallet with which the cylin- der module is secured to the pallet. Material losses Never tilt the cylinder module excessively. Contacts bet- ween the casing and the floor can damage the paintwork. 1 Captive nut on the bottom of the cylinder module 2 Adjustable foot with nut for fitting with an open-ended spanner...
iNSTaLLaTiON installation Pushing the cylinder module towards the function module Pushing the cylinder and the function modules together f Push the cylinder module carefully towards the function Note module, so that the rear r.h. adjustable foot of the cylinder module is near the recess in the joining bracket. An air hose to capture the differential pressure runs along the l.h.
Page 15
iNSTaLLaTiON installation Fitting the horizontal locking bracket to the front To make yourself room for the assembly, you can temporarily unhook the high limit safety cut-out retaining bracket. f Connect the function module and cylinder module at the f Undo the screws on the high limit safety cut-out retaining front by securing one horizontal locking bracket each at the bracket.
iNSTaLLaTiON installation Making the push-fit connection Undoing the push-fit connection The connector must be in its relaxed position before the pipe is If the push-fit connectors later need to be undone, proceed as inserted. In this position, there is a small gap between the screw follows: cap and connector body.
iNSTaLLaTiON installation „Heating return“ connection Note Suitable appliances for water softening, as well as for filling and flushing heating systems, can be obtained via trade suppliers. Minimum flow rate The appliance is designed in such a way that no buffer cylinder is required to provide hydraulic separation of the flow in the heat pump circuit and the heating circuit in conjunction with area hea- ting systems.
iNSTaLLaTiON installation Condensate drain and overpressure valve Safety valve f Check the position of the internal condensate pump in the The appliance is a sealed unvented DHW cylinder. Provide the function module. The condensate pump must fully rest on the appliance with a pressure relief valve.
Page 19
iNSTaLLaTiON installation 5.9.2 Control panel WARNING Electrocution Only components that operate with safety extra low voltage (SELV) and that ensure secure separation from the mains voltage supply may be connected to the low voltage terminals of the appliance. Connecting other components can make parts of the ap- pliance and connected components live.
Page 20
iNSTaLLaTiON installation 5.9.4 Control voltage 5.9.6 External pumps ( PWM ) Note The power supply to the external pumps is not provided via the appliance. XD03 Contact for Power-OFF command by the power supply uti- lity (option) Steuerung Control Mi AUF Mixer open Mi ZU Mixer close...
Page 21
iNSTaLLaTiON installation 5.9.8 Connecting sensors XD04 External terminals ( S afety extra low voltage ) Outside temperature sensor Mixer circuit flow temperature sensor 1 Sensor well for the cylinder temperature sensor (economy Room temperature sensor mode/buffer mode) Solar temperature sensor 2 Sensor well for the cylinder temperature sensor (Comfort) Temperature sensor for second DHW cylinder No function Outside temperature sensor AFS 2...
iNSTaLLaTiON installation 5.9.9 CAN BUS Internet Service Gateway The Internet Service Gateway (ISG) enables you to operate the Connecting the external programming unit appliance within your local home network and via the internet when on the go. Note Check whether the room in which the external pro- gramming unit is installed receives a lot of warmth, for example sunlight.
Page 23
iNSTaLLaTiON installation f Refit the protective caps on the fill valves. Determine the fill pressure Volume of the diaphragm expansion vessels integrated into the appliance Expansion vessel pre-charge pressure ( P0 ) 0.75 If the height difference ∆h between the highest point of the heating system and the diaphragm expansion vessel is no more than 6 m, the diaphragm expansion vessel can be used without any changes being required.
iNSTaLLaTiON installation f Determine the „PRESSURE HTG CIRC“ value for one of the 5.11.2 Installing front panel of the function module three favourites. For this, navigate from the default display to f Attach the lower front panel of the function module using the „FAVOURITES“...
iNSTaLLaTiON installation f Connect the bus cable to the programming unit. The BUS f Push the external hose and the thermal insulation slightly up cable must run upwards with the jumper in the l.h. side. so that the internal hose of the air hose protrudes slightly. f Insert the fascia from the top into the fascia frame.
iNSTaLLaTiON Commissioning 5.13.1 Silencer Fit silencers as near as possible to the appliance into the extract air and the supply air flows. Fit a silencer just upstream of bedrooms. If a room with a high noise level needs to be ventilated, install additional silencers in the supply air pipe or extract air pipe of this room to reduce sound transmission to adjacent rooms.
iNSTaLLaTiON Commissioning - Has the condensate hose been routed correctly? 6.1.7 High limit safety cut-out - Was a vessel placed beneath the safety valve discharge hose? With ambient temperatures of below -10 °C, it is possible that the high limit safety cut-out of the electric emergency/booster 6.1.2 Ventilation system heater may trip.
iNSTaLLaTiON appliance shutdown Appliance shutdown Troubleshooting Exhaust air fan is catching WARNING Injury There will be no ventilation if the appliance is taken out If the exhaust air fan drags, return it into its correct position. of use. This may result to the development of mould fun- gus and damage to the building.
iNSTaLLaTiON maintenance and cleaning Circulation pump Maintenance and cleaning If the LED on the heating circuit pump flashes red even though WARNING Electrocution there is an active heat demand, disconnect the power supply for f Prior to commencing any service or cleaning work, 30 seconds.
iNSTaLLaTiON maintenance and cleaning Cleaning the outdoor air filter The outdoor air filter is fitted downstream of the cross-counter- current heat exchanger. f Remove the dirt grille fitted above the condensate pan by compressing it from its sides and removing it upwards. 1 Upper front panel f Check the defrost pan drain and clean it, if required.
iNSTaLLaTiON maintenance and cleaning f Spray water across the evaporator fins. f Remove the water from the appliance using a wet suction device. f Remove contaminants and blockages. Note Check the condensate drain regularly, at least once a year. Cleaning the condensate drain Check the condensate drain regularly.
Page 32
iNSTaLLaTiON maintenance and cleaning Checking the diaphragm expansion vessels 1 Fill valve of the expansion vessel f Remove the protective caps from the fill valves on the expan- sion vessels. 1 Cap valve f Close the cap valve and depressurise the expansion vessel by draining the cap valve.
iNSTaLLaTiON Specification 10.9 Data table The output data refers to new appliances with clean heat ex- changers. The power consumption of the integral auxiliary drives represents the maximum value and may vary subject to operating point. The power consumption of the integral auxiliary drives is included in the output details of the appliance (to EN 14511).
Page 41
iNSTaLLaTiON Specification LWZ 5 CS Premium LWZ 8 CS Premium Versions Refrigerant R410A R410A Refrigerant charge 2.95 2.95 equivalent (CO 6.16 6.26 Global warming potential of the refrigerant (GWP100) 2088 2088 IP rating IP1XB IP1XB Filter class, extract air ISO Coarse > 60 % (G4) ISO Coarse > 60 % (G4) Filter class, supply air ePM10 ≥...