OPERATION AND INSTALLATION
Centralised ventilation unit with heat recovery
» LWZ 130 J
» LWZ 130 JE

Advertisement

Table of Contents
loading

Summary of Contents for STIEBEL ELTRON LWZ 130 J

  • Page 1 OPERATION AND INSTALLATION Centralised ventilation unit with heat recovery » LWZ 130 J » LWZ 130 JE...
  • Page 2: Table Of Contents

    11.2 Recommissioning ����������������������������������������������� 14 are supervised. Settings ����������������������������������������������������� 14 - Fix the appliance in position as described in 12.1 Parameter �������������������������������������������������������� 14 chapter "Installation / Preparations". 12.2 Actual values ���������������������������������������������������� 15 12.3 Code ��������������������������������������������������������������� 15 | LWZ 130 J www.stiebel-eltron.com...
  • Page 3: General Information

    General information is identified by the adjacent symbol. f Read these texts carefully. Note All measurements are given in mm unless stated oth- erwise. Symbol meaning Material losses (appliance damage, consequential losses and environmen- tal pollution) Appliance disposal www.stiebel-eltron.com LWZ 130 J |...
  • Page 4: Safety

    The membrane helps to recover moisture from the extract air and transfer it to the supply air. This prevents the relative humidity in the rooms from dropping too low during the winter months. | LWZ 130 J www.stiebel-eltron.com...
  • Page 5: Settings

    Use the Touch-Wheel to select a parameter or value in the The qualified contractor can configure the humidity protection menu. control unit with parameters. If you turn the Touch-Wheel quickly, the increment size chang- es after a while. www.stiebel-eltron.com LWZ 130 J |...
  • Page 6: Activating Time Programs

    Press the "OK" button to save the set for qualified contractors in the "Troubleshooting" chapter. value for a parameter. If you do not confirm the parameter change with the "OK" button, your change will be lost. | LWZ 130 J www.stiebel-eltron.com...
  • Page 7: Switching Off The Appliance

    In the case of overlapping time programs, the program Note with the highest number takes priority. Insects may gather in front of the outdoor air filter and be drawn into the appliance through the outdoor air duct during appliance operation. www.stiebel-eltron.com LWZ 130 J |...
  • Page 8: Troubleshooting

    On M5 and F7 filters, the direction of flow is indicated by an arrow on the side of the filter. In the case of G4 filter mats, the blue side is the inflow side, i.e. the dirty side. | LWZ 130 J www.stiebel-eltron.com...
  • Page 9: Installation

    Note The maximum available external pressure (see chapter "Specification / Data table") must not be exceeded. www.stiebel-eltron.com LWZ 130 J |...
  • Page 10: Appliance Description

    Otherwise material losses may arise due to the formation of condensation. Ensure the appliance is level after installation. The installation room must have an adequate condensate drain with siphon. | LWZ 130 J www.stiebel-eltron.com...
  • Page 11: Installation

    This could cause the con- densate drain connection to leak or break off. f Secure the condensate drain hose, e.g. to the ceiling. www.stiebel-eltron.com LWZ 130 J |...
  • Page 12: Air Ducts

    Never link cooker hoods to the ventilation system. air duct. Install these silencers as close as possible to the ap- pliance, so that noise is suppressed at an early stage. We recommend installing additional silencers if required to avoid sound transmission. | LWZ 130 J www.stiebel-eltron.com...
  • Page 13: Electrical Connection

    Insulation stripping length Material losses f Prepare the end of the cable by stripping the sheath and Observe the MCB/fuse protection required for the appli- insulation. ance (see chapter "Specification / Data table"). www.stiebel-eltron.com LWZ 130 J |...
  • Page 14: Commissioning

    Use this parameter to adjust the supply air flow rate during com- f Set the current time. missioning. The offset relates to standard ventilation. The offset „ „ P81 00:00 - 23:59 is converted internally as a percentage for the other fan stages. | LWZ 130 J www.stiebel-eltron.com...
  • Page 15: Actual Values

    „ „ Outdoor air temperature °C „ „ Extract air dew point °C 1 Condensate pan fixing screws „ „ Supply air fan drive output 2 Condensate pan „ „ Exhaust air fan drive output www.stiebel-eltron.com LWZ 130 J |...
  • Page 16: Troubleshooting

    Push the fan units back into the appliance. f Reconnect the fan cables. f Fit the control panel cover. f Slide the cross-countercurrent heat exchanger back into the appliance. f Push the wedge back in again. f Fit the condensate pan. | LWZ 130 J www.stiebel-eltron.com...
  • Page 17: Specification

    Diameter g06 Supply air Diameter 16.2 Fan diagram The graphs show hydraulic curves for examples of air distribution systems. Application range Maximum fan curve Air flow rate [m³/h] System curves Average value, static pressure [Pa] www.stiebel-eltron.com LWZ 130 J |...
  • Page 18: Wiring Diagram

    Supply air fan power cable Exhaust air fan power cable Internal float switch Outdoor air temperature sensor X11 Remote control X16 Extract air temperature and humidity sensor X21 Exhaust air fan control cable X22 Supply air fan control cable | LWZ 130 J www.stiebel-eltron.com...
  • Page 19: Data Table

    -15-40 -15-40 Application range, extract air (temperature) °C 15-35 15-35 Min. ambient conditions, installation room (temperature) °C Max. ambient conditions, installation room (temperature) °C Available external pressure at max. air flow rate Heat recovery level www.stiebel-eltron.com LWZ 130 J |...
  • Page 20 This will not affect warranties issued by any importers. Environment and recycling We would ask you to help protect the environment. After use, dispose of the various materials in accordance with national regulations. | LWZ 130 J www.stiebel-eltron.com...
  • Page 21 „ Mode of backlighting Auto | On  | Off Auto „ „ Illumination duration „ „ Lower standard display Off | Time  | Set room tempera- ture  | Extract air temperature  | Extract air humidity www.stiebel-eltron.com LWZ 130 J |...
  • Page 22 FILTER INSPECTION LOG Filters in appliance Date filter dirty filter cleaned filter changed Filters in extract air/supply air apertures (if present) Date filter dirty filter cleaned filter changed | LWZ 130 J www.stiebel-eltron.com...
  • Page 23 NOTES www.stiebel-eltron.com LWZ 130 J |...
  • Page 24   Deutschland Verkauf Tel. 05531 702-110 | Fax 05531 702-95108 | info-center@stiebel-eltron.de STIEBEL ELTRON GmbH & Co. KG Kundendienst Tel. 05531 702-111 | Fax 05531 702-95890 | kundendienst@stiebel-eltron.de Dr.-Stiebel-Straße 33 | 37603 Holzminden Ersatzteilverkauf Tel. 05531 702-120 | Fax 05531 702-95335 | ersatzteile@stiebel-eltron.de Tel.