DTK-TSS4D DRY CONTACT OPERATION

The Dry Contacts are a SPDT Form 1C circuit rated 48VDC/0.6A, designed for low voltage or control
signals only, and activate if the Phase leg loses its surge protection. The Dry Contacts are accessed
by a three position terminal block (#16-28 AWG). The positions are marked Common (C),
Normally Open (NO), and Normally Closed (NC). If the surge protection is lost, the contacts will
reverse; Normally Open will close and Normally Closed will open.
There is no change to the Common (C)
Revised By: R. Mitchell 11-6-17
Approved By: R. Mitchell 11-6-17
INSTALL INSTRUCTIONS
Illustrations Page
120 VAC Power In.
Enclosed In Conduit.
Supply Wiring
25 Amp Max
S
P
(L) BLK.1
(L) BLK.1
D
(N) WHT.
(N) WHT.
EQUIPMENT
(G) GRN.
(G) GRN.
GND.
L-N
L-G
N-G
120
120
0
DITEK Technical Support Available 24/7
DTK-TSS4D
INPUT
OUTPUT
LINE
LINE
NEUTRAL
NEUTRAL
GROUND
DTK-TSS4D
DRY CONTACT
NO
C
OUT
1-888-472-6100 www.ditekcorp.com
120 VAC Power To
Protected Equipment.
3' Of Conductor
Length
NC
120VAC(+)
LOAD: 48VDC, 0.6AMP (MAX)
Doc # INT-100086-001
Part No. 191518 Rev. 6
-
NEUTRAL(
)

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DTK-TSS4D and is the answer not in the manual?

Table of Contents