NOTE: Inspect for shipping damage and notify freight carrier or store where purchased immediately if damage is present. To avoid risk of personal
injury and property damage, if the product appears to be malfunctioning or shows signs of corrosion, call a licensed professional immediately. Current
copies of the Product manual can be viewed at www.amtrol.com. Use proper safety equipment when installing.
THIS IS THE SAFETY ALERT SYMBOL. IT IS USED TO ALERT YOU TO POTENTIAL PERSONAL INJURY AND OTHER HAZARDS.
OBEY ALL SAFETY MESSAGES THAT FOLLOW THIS SYMBOL TO REDUCE THE RISK OF PERSONAL INJURY AS WELL AS
PROPERTY DAMAGE.
READ
INSTALLATION & OPERATION INSTRUCTIONS.
FAILURE TO FOLLOW THE INSTRUCTIONS AND WARNINGS IN
THE MANUAL MAY RESULT IN SERIOUS OR FATAL INJURY AND/
OR PROPERTY DAMAGE, AND WILL VOID THE PRODUCT
WARRANTY.
THIS PRODUCT MUST BE INSTALLED BY A
LICENCED PROFESSIONAL. FOLLOW ALL APPLICABLE LOCAL
AND STATE CODES AND REGULATIONS, IN THE ABSENCE OF
SUCH CODES, FOLLOW THE CURRENT EDITIONS OF THE
NATIONAL PLUMBING CODE AND NATIONAL ELECTRIC CODE,
AS APPLICABLE.
EXPLOSION OR RUPTURE HAZARD. THE
EXPANSION TANK MUST BE OPERATED SO
THAT THE PRESSURE DOES NOT EXCEED THE MAXIMUM
WORKING PRESSURE.
EXPLOSION OR RUPTURE HAZARD A relief
valve must be installed to prevent pressure in
excess of local code requirement or maximum working pressure
designated in the Product Manual, whichever is less. Do not expose
Product to freezing temperatures or temperatures in excess of 240° F.
INSTALLATION & OPERATION INSTRUCTIONS
CAREFULLY
THE
PRODUCT
EXTROL
HYDRONIC EXPANSION ABSORBERS (ASME)
Models 35-LBC through 600-LBC
Partial Acceptance Bladder Models
Do not adjust the pre-charge or re-pressure this Product except for any
adjustments required at the time of initial installation, especially if
Product corroded, damaged or with diminished integrity. Adjustments to
pre-charge must be done at ambient temperature only.
properly size the Product or follow these instructions may result in
excessive strain on the system lead to Product failure, serious or fatal
personal injury, leakage and/or property damage.
Potable Water and Radiant Heating Warning.
This Product must not be used in radiant heating,
potable water or open systems of any kind. These systems contain
oxygenated water which will cause internal corrosion and premature
Product failure. Use a Therm-X-Trol
Radiant Extrol
for radiant heating systems. Mount vertically only. Do
®
not install on dead-end pipe.
This product can expose you to chemicals
including lead, which is known to the State of
California to cause cancer and birth defects or other reproductive harm.
For more information go to www.P65Warnings.ca.gov.
LBC SERIES
®
for potable water systems and a
®
Failure to

Advertisement

loading

Summary of Contents for Amtrol Extrol LBC SERIES

  • Page 1 Current copies of the Product manual can be viewed at www.amtrol.com. Use proper safety equipment when installing. THIS IS THE SAFETY ALERT SYMBOL. IT IS USED TO ALERT YOU TO POTENTIAL PERSONAL INJURY AND OTHER HAZARDS.
  • Page 2: Operating Instructions

    Check to make sure this is the correct pre-charge pressure specified for the system. The AMTROL expansion tank may be placed in any convenient position 2. If the tank pre-charge pressure needs to be changed on a dry system within the mechanical room (or building). If multiple tanks are installed, follow the following procedure: they should all be on the same level.
  • Page 3 Suggested Piping Diagram AMTROL RETURN AIR ELIMINATOR AMTROL AIR SEPARATOR ISOLATION VALVE C.W.S. SUPPLY DRAIN AMTROL AUTOMATIC DRAIN FILL VALVE AMTROL EXTROL ® TRI-FLOW TANK VALVE SUCTION PUMP DIFFUSER Alternate Piping Diagram ALTERNATE AIR SEPARATOR LOCATION RETURN AMTROL AIR ELIMINATOR...
  • Page 4 1400 Division Road, West Warwick, RI USA 02893 T: 800.426.8765 www.amtrol.com © 2019 Worthington Industries Inc. Part #: 9017-095 (06/19) One or more features of this product are covered by U.S. patents, visit www.amtrol.com/patents for more information.

This manual is also suitable for:

Extrol 35-lbcExtrol 600-lbc