Pr.72 = 6 STEP RUN & REPEAT from STEP-2
This mode is similar to mode4.
From STEP1 to STEP5, its operation is exactly the same as mode4.
After STEP5, the procedure jumps to STEP2 and repeat.
START: SETP1-->STEP2 ~ -->STEP5-->STEP2 ~ -->STEP5-->STEP2 ~ -->STEP5 ........
1
T1

12.2 Auto Run Status Output

During AUTO RUNNING, there are special DOx functions reserved for AUTO STEP EQUAL application. (Refer to
Section 9.21~9.30)
EXAMPLE:
If user wishes to activate the DOx outputs when inverter is auto running,
if LET
DO1(22), select STEP2
DO2(23), select STEP3
DO3(24), select STEP4
THEN
DO1 terminal will become ON, while the inverter is running at STEP2
DO2 terminal will become ON, while the inverter is running at STEP3
RELAY terminals will become ON, while the inverter is running at STEP4
Pr.00
Pr.21
Pr.24
Pr.27
Pr.19
Pr.73
DO1(22)
DO2(23)
RELAY(24)
EXAMPLE: Timing Relationship waveform of "STEP EQUAL OUTPUT " Function.
2
3 4 5
2
T2 T3 T4 T5 T2 T3 T4 T5 T2 T3 T4 T5
Pr.74
Pr.75
Pr.76
3 4 5
2
3 4 5
48
time
time
time
time