8. Selection of Digital input function

The terminals DI1, DI2, DI3, & DI4 are multi-functioned Digital Input terminals.
【Note】All the DIx terminals are scanned once every 5.0 ms.
These four terminals are exactly identical in its hardware/software configurations.
When left open, they are OFF. And will become ON when connected to DCOM.
Each input terminal can be configured individually by corresponding DIx_SELECT parameters.
The four DIx_SELECT parameters are:
Pr.41 -- DI1_SELECT, used for DI1
Pr.42 -- DI2_SELECT, used for DI2
Pr.43 -- DI3_SELECT, used for DI3
Pr.44 -- DI4_SELECT, used for DI4
Pr.03 -- DI5_SELECT, used for DI5 (Sec. 1.2 RUN mark terminal)
Pr.04 -- DI6_SELECT, used for DI6 (Sec. 1.2 REV mark terminal)
Selection Table of Digital input function
Pr.41,42,43,44
FUNCTION
0
NULL
1
EMS
2
SPD3
3
SPD2
4
SPD1
5
JOG
6
OH
7
TMIA
8
ON_BB
9
FJR
10
RJR
11
TMIB
12~14
Reserve
15
U/D COUNTER CLEAR
16
U/D COUNTER LOAD
17
U/D COUNTER HOLD
18
OFF_BB
19
U/D COUNTER UP
20
U/D COUNTER DOWN
21
ALARM CLEAR
22
SET1 (FF1)
23
CLR1 (FF1)
24
SET2 (FF2)
25
CLR2 (FF2)
26
SET (FF1&FF2)
27
CLR (FF1&FF2)
28
CLK Input
29
Reserve
30
/OH
31
Normal/Auto SW
32~35
Reserve
36
TMIC
37~47
Reserve
48
Speed Hold
49
Reserve
50
PID Enable
51
PID Hold
52
PID Clear
53
PID Preset
54
PID Bias Enable
55
PID Boost Enable
56-68
Reserve
69
DC-BRAKE1
70
DC-BRAKE2
71
DC-BRAKE3
72
Sensor-Less Mode Change
73
RUN function
74
REV function
75
POWER-CONTROL select
76
FORWARD INHIBIT
COMMENT
NO FUNCTION
EMERGENCY STOP
SPEED SET
SPEED SET
SPEED SET
JOG SPEED SET
OVER HEAT ERROR,
TIMER INPUT for TYPE A
BASE BLOCK if DIx is ON
FORWARD JOG RUN
REVERSE JOG RUN
TIMER INPUT for TYPE B
SET UP/DOWN COUNTER to Pr.16
SET UP/DOWN COUNTER to Pr.15
HOLD "Output HZ" to UP/DOWN COUNTER
BASE BLOCK if DIx is OFF
INCREASE UP/DOWN COUNTER
DECREASE UP/DOWN COUNTER
CLEAR ALARM WHEN ALARM OCCUR
SET input of Flip/Flop-1
CLEAR input of Flip/Flop-1
SET input of Flip/Flop-2
CLEAR input of Flip/Flop-2
SET input to both FF1 & FF2
CLEAR input to both FF1& FF2
Input CLOCK to Timer/Counter Block
OVER HEAT ERROR, (input open)
Change Over Switch for Normal or Auto Run
TIMER INPUT for TYPE C
Hold Output Speed
PID Enable
PID Integrator Hold
PID Integrator Clear
Preset PID Integrator
PID Bias Enable
PID Boost Enable
DC injection brake use AI1 as brake level
DC injection brake use AI2 as brake level
DC injection brake use AI3 as brake level
Select or non-select the SENSOR-LESS mode
Select standard RUN function, Refer to Sec.6
Select standard REV function, Refer to Sec.6
Select AI2 or AI3 for Power Control input
Forward run inhibit
32