3.5.1 Finch II Generated Alarms
Alarm
Alarm Set By
Spill
Factory (Pre-Set)
High-High
SensorLink
Fill
Finch II
Fall
Finch II
Fail
Finch II and TD100
Transmitter
2 Lo
Factory (Pre-Set)
*Refer to TPM051 Finch II Programming Manual
3.5.1.1
Spill
Spill is an approaching overfill condition. TD100 transmitters and probes are factory set at 7.1" below
the tank top.
The TD100 transmitter is the source of this alarm. Spill alarms are indicated by showing "SPill" on the
display and may activate a relay depending on the user's configuration.
3.5.1.2
High-High
The High-High alarm is the maximum safe volume of the tank.
The TD100 transmitter is the source of this alarm. The HH alarm is activated by a measured volume
equal to or exceeding the alarm level set during programming. High-High alarms are indicated by
alternately flashing "HH" along with the current level on the Display and may activate a relay depending
on the user's configuration.
3.5.1.3
Fill/Fall
The Fill alarm is used to warn the operator when the loading process is nearing maximum capacity and
the Fall alarm is used when a minimum volume of product must be retained in the tank to prevent pump
damage.
The Fill and Fall alarms are programmed by the operator using the Finch II or 5332INT displays.
The Finch II display is the source of this alarm. Fill/Fall alarms are indicated by flashing Fill or Fall and the
level on the display. The Horn relay is activated by default on a Fill alarm and no relay is activated by
default on a Fall alarm.
TPM 057
Condition
Tank volume is in overfill state
TM
The maximum safe volume of the tank
(set by the user)
User determined tank levels for use
when filling the tank.
User determined tank levels for use
when draining the tank.
System failures such as internal
transmitter errors, probe faults or loss
of communications are reported by
the Spill/Fail Relay and shown on the
Finch II display
Tank volume is less than 2.5" from the
top of the shorting block (too low for
correct readings)
Version 1.0, May 31, 2018
OVERVIEW
TD100 Installation and Operation Manual
Control Relay
Assignments
Programmable*
Programmable*
Programmable*
Programmable*
Programmable*
No Relay - Factory Pre-
Set
Page | 12