Daikin VRV Series Technical Data Manual page 4

Outdoor units
Hide thumbs Also See for VRV Series:
Table of Contents

Advertisement

1
Specifications
1-3
ELECTRICAL SPECIFICATIONS
(50HZ)
Current
Nominal
running current
1
(RLA)
Starting current (MSC)
1
Z-max
Minimum Ssc value
Minimum circuit amps
(MCA)
Maximum fuse amps (MFA) A
Full load amps (FLA)
Voltage range
Minimum
Maximum
Wiring
For Power
connections
Supply
For connection
with indoor
Power Supply Intake
Notes
3
• Outdoor Units • VRV HEAT RECOVERY • REYHQ16-24P
REYHQ16PY1B
Cooling
A
16.4
A
4
Text
-
kVa
2,436
A
37.0
50
A
1.4
V
342
V
456
Quantity
5
Remark
Quantity
2
Remark
MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker)
RLA is based on following conditions : indoor temperature : 27×CDB/19×CWB , outdoor temperature : 35×CDB
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or
In accordance with EN/IEC 61000-3-11(1), respectively EN/IEC 61000-3-12(2), it may be necessary to consult the
distribution network operator to ensure that the equipment is connected only to a supply with Zsys(4) <= Zmax,
• VRV Systems • Outdoor Units
REYHQ20PY1B
19.1
79
0.27
2,332
50.0
63
1.9
342
456
5
Earth wire include
2
F1 - F2
Both indoor and outdoor unit
MSC means the maximum current during start up of the compressor
Maximum allowable voltage range variation between phases is 2%
Select wire size based on the value of MCA or TOCA
TOCA means the total value of each OC set
above listed range limits
respectively Ssc(3) >= minimum Ss
REYHQ22PY1B
REYHQ24PY1B
22.2
21.8
88
88
0.25
0.24
2,042
2,228
53.1
63.0
63
80
2.1
2.4
342
342
456
456
5
5
2
2