6.8.1.2 Connection of two batteries with different charging/
discharging currents
You may connect two batteries: The first has a charging/discharging current limit of 20 A and the
second 10 A.
Procedure:
The DC terminals A and B must be switched parallely using the jumpers provided.
The battery limited to a charging/discharging current of 20 A must be connected to the terminal
blocks A+ and A-.