Sauter Components AVM 234S Series Instructions Manual

Sauter Components AVM 234S Series Instructions Manual

Valve actuator with sut positioner

Advertisement

Quick Links

AVM 234S: Valve actuator with SUT positioner

How energy efficiency is improved

Automatic adaptation to valve, precision control and high energy efficiency with minimal operating noise.

Areas of application

For use with through or three-way valves in the V/BUD and V/BUE DN65...150 series, and V/BUG,
V/BUS, VUP and V/B6R DN15...150. For controllers with continuous output (0...10 V or 4...20 mA) or
switching output (2-point or 3-point control).

Features

Pushing force of at least 2500 N
Stepping motor with SUT (Sauter Universal Technology) electronic control unit and electronic
load-dependent cut-off
Automatic detection of control signal applied (continuous or switching), indicated by two LEDs
The type of characteristic (linear, quadratic or equal-percentage) can be set on the actuator
Automatically adapts to valve stroke between 8 and 49 mm; captive even in the event of a
power failure
Direction of travel can be selected via screw terminals when making electrical connection or
remotely
Coding switches for selecting the characteristic and the running time (2, 4 or 6 s/mm)
Lever for external manual adjustment, with motor cut-off, and for triggering a re-initialisation
Easy assembly with valve; spindle is connected automatically when control voltage is applied
The availability of numerous adaptors enables the actuator to be fitted to third-party valves

Technical description

Power supply 230 V with modules or direct connection for 24 V~ or 24 V=; continuous activa-
tion also permissible at 230 V
Two-part housing made of fire-retardant yellow plastic and seals to IP66
Maintenance-free gearbox of sintered steel, gearbox plate of steel
Patented actuator–valve coupling
Mounting column made of stainless steel; mounting bracket (for fitting the valve) of cast light
alloy
Electrical connections (max. 2.5 mm²) with screw terminals
Three pre-scored cable inlets for M20×1.5 (2×) and M16×1.5
Installation position: vertically upright to horizontal, but not upside down
Type
Run time
s/mm
Valve actuator for valves: VUD / BUD, VUE / BUE, VUG / BUG, VUS / BUS and VUP
2 / 4 / 6
AVM 234S F132
matching with assembly for valve series: V6R / B6R
2 / 4 / 6
AVM 234S F132-5
2 / 4 / 6
AVM 234S F132-5
1)
Positioner:
Control signal 1
Control signal 2
Position feedback signal
Power supply
24 V∼
24 V=
with accessories 230 V~
Power consumption
Stroke
Max. temperature of medium
Permitted ambient temperature
Permitted ambient humidity
1)
Also for 2-point or 3-point depending on the connection for 24 V~
2)
Design the transformers for this value, otherwise functional faults may occur.
3)
If the temperature of the medium is higher (180 ° C or 240 ° C), an adaptor is required (see accessor ies)
Stroke
Pushing
mm
14...40
2500
14
2500
40
2500
0...10 V, R i > 100 kΩ
Starting point U 0
4...20 mA, R i = 50 Ω
Control span ∆U
0...10 V, load > 2.5 kΩ
Switching range X sh
± 20%, 50...60 Hz
Degree of protection
± 15%
Protection class
± 15%
Response time for 3-point
2)
10 W
18 VA
8...49 mm
Wiring diagram
3)
130 ° C
Dimension drawing
–10...55 ° C
Fitting instructions
< 95% rh
Material declaration
without condensation
Power
Weight
1)
force
supply
N
24 V~/=
24 V~/=
24 V~/=
0 or 10 V
10 V
300 mV
IP 66 (EN 60529)
III (IEC 60730)
200 ms
A10357
M10356
MV 505919
MD 51.377
Sauter Components
100 %
0 %
0 V
kg
4.1
4.1
4.6
51.377/1
M
Y07552
Output signal y
10 V
B07650
7151377003 10

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the AVM 234S Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Sauter Components AVM 234S Series

  • Page 1 Also for 2-point or 3-point depending on the connection for 24 V~ Design the transformers for this value, otherwise functional faults may occur. If the temperature of the medium is higher (180 ° C or 240 ° C), an adaptor is required (see accessor ies) Sauter Components 7151377003 10...
  • Page 2 90 s. However, the actuator will try to overcome the blockage during this time. If the blockage can be rectified, the normal control function is activated again and the feedback signal is restored. No initialisation is performed with 2-point or 3-point control. The feedback signal is inactive. Sauter Components 7151377003 10...
  • Page 3 "OPEN" position Lower LED lit green: actuator stationary, last direction of running "OPEN" No LED lit: no power supply (terminal 2a or 2b) Both LEDs flashing red and green: actuator is in manual mode Sauter Components 7151377003 10...
  • Page 4 EMC Directive 2004/108/EC Low-Voltage Directive 2006/95/EC EN 61000-6-2 EN 60730-1 EN 61000-6-4 EN 60730-2-14 Over-voltage category III Degree of pollution III *) HF immunity restriction. Feedback signal between 80 MHz and 1000 MHz: criteria B, otherwise criteria A Sauter Components 7151377003 10...
  • Page 5 28s ± 1 40s ± 1 80s ± 2 1 2 3 56s ± 2 80s ± 2 160s ± 4 1 2 3 84s ± 4 120s ± 4 240s ± 8 = factory setting B10377 Sauter Components 7151377003 10...
  • Page 6 0372336 240 Type AVM 234S F132 AVM 234S F132-5 AVM 234S F132-6 M10356a T (° C) a (mm) b (mm) 0372336 69,4 Printed in Switzerland 109,4 Right of amendment reserved M10217 © Fr. Sauter AG, CH-4016 Basle 7151377003 10 Sauter Components...

This manual is also suitable for:

Avm 234s f132Avm 234s f132-5

Table of Contents

Save PDF