Pulsafeeder. Warranty parts returned as defective which test good will be sent back freight collect. No credit will be issued on any replacement electronic parts.
8. ABC SERIES LINE UP AND OPTIONS ....16 1. INTRODUCTION The Pulsafeeder ABC Controllers are used to control total dissolved solids (TDS) in steam boiler systems, in terms of electrical conductivity measured in microsiemens per cm (µS/cm).
2. INSTALLATION Fig. 1, Typical Installation Diagram A. LOCATION: The ABC Series Controllers are designed for ease of installation. Select a mounting location convenient to electrical and plumbing connections and easily accessible by the operator for cleaning and maintenance. The enclosure is corrosion resistant and will stand up to most industrial envi- ronments.
Page 5
(Refer to Fig. 2, Controller Dimensions). C. ACCESSORIES: (Available through your Pulsafeeder distributor or sales representative, but not included as standard) Boiler Conductivity Timed Sample: 1. Blowdown valve, solenoid and strainer or motor oper- ated ball valve.
Page 6
JP4 and JP5 are relay driven AC outputs, they change simultaneous- ly and have a maximum output of 5 amps. The ABC 50 has two fuses for protection, a 1 amp fuse for the controller power supply, and a 5 amp fuse for the relay output. Part numbers can be found in the Trouble Shooting section.
Page 7
NOTE: Do not connect the ground wire to the Shield (SHD) input. It is for the shield of the probe cable only. NOTE: The ABC 50 does not support temperature compensation. A tempera- ture compensated probe may be used, but will yield non-temperature com-...
Use the test switch to force a system blow down if necessary for gathering a sample of system water. NOTE: For best results, calibrate the ABC 50 at a conductivity as near to the trip point as possible.
Page 9
Fig. 7 Position Trip Point Knob Fig. 8 Turn Cal Adjust Knob 3) Set the trip point knob to the conductivity measured by the hand held meter (Fig. 7). 4) Turn the cal knob fully counter clockwise and momentarily activate the test switch (Fig.
Page 10
D. JUMPER SELECTIONS Fig. 10, Jumper connection locations. Jumper connection JP6 through JP15 Jumper connection JP1, 2, 3, 17, and 18 High Voltage connections The ABC controller can be operated in either timed or continuous mode, the ABC controller has jumpers for selection of the operating mode and the time intervals (Fig.
JUMPER FUNCTION USER CHOICE JP2, JP17 Selects 50 Hz operation Factory installed JP3, JP18 Selects 60 Hz operation Factory installed Selects Timed Sample Mode Select either JP6 or JP7 Selects Continuous Sample Mode Selects a 24 hour time between sample intervals Select one of JP8 - JP11 Selects a 8 hour time between sample intervals JP10...
Without some method to compensate for these changes, a unit will consist of the conductivity caused by the particular level of dissolved solids, plus or minus the effect of temperature. The ABC 50 Controller is not compensated for temperature. The user is responsible for maintaining consistent probe tempera-...
6. TROUBLE-SHOOTING GUIDE SYMPTOM POSSIBLE CAUSE SOLUTION Power light is not on Blown fuse Replace fuse with Bussman PCC1 (1 amp) or equivalent. No power supplied Check line circuit breaker. to unit Relay fuse blows repeatedly External component Disconnect external loads. If defective this prevents the fuse from blowing, plug each external load in, one-by-one, until the...