Software Setup Based on Specific Application – Multiple applications exist for this product. The unit is
shipped preprogrammed for a range of applications with the ability to be reprogrammed to meet others.
Below are the most prevalent applications.
Application one - single exhaust source single speed blower
Application two - multiple exhaust source blower motors of different ratings
Application three - single exhaust source multi-speed blower
Applications one and two are factory default settings and no further software setup is necessary to meet
these applications.
Applications one and two sequence:
When the CT input to CT terminal block (TB2) labeled "HI" goes active, the unit blower will go
to high speed.
o If application one, sequence ends here.
When the CT input to CT terminal block (TB2) labeled "MED" goes active, the unit blower will
go to medium speed.
When the CT input to CT terminal block (TB2) labeled "LO" goes active, the unit blower will go
to low speed.
See Nominal CFM section for typical CFM air delivery.
Application three – software configuration is required in order to activate the multi-speed functionality
of this product when being used with a multi-speed vent hood. For instruction on how to configure for
multi-speed blower interlock, see the Multi-Speed Setup section.