Installation & Operating Manual
---------------------------------------------------------------------------------------
Packaged Make-Up Air
No Heat Models EM-MC00*, EM-MD00*, EM-ME00*, EM-MF00*, EM-MG00*
Included With This Product
Permanent washable air filter
Powered inlet damper
(2) temperature sensors
(1) current transformer (CT doughnut)
Chain kit for ceiling installations
Other Requirements
Low voltage (Class II type) wiring when using supply CT doughnut to control Make-Up Air unit
High voltage wiring
Fresh air intake wall or roof vent
Inlet/outlet ductwork
Application
This product aids in preventing building depressurization where there is single or multi-source exhaust
points, coupled with a tight building envelope such as:
Single, large exhaust source
- Kitchen range hood
Multiple exhaust sources
- Bathroom fan, fireplace, dryer, gas furnace, dryer, etc.
Note
In applications where the exhaust fan utilizes a multi-speed blower, this product has the ability to
sense each fan speed by monitoring the amperage of the exhaust fan motor. After completing the
mechanical portion of the installation, see Multi-Speed Setup for further details explaining how
to utilize this unique feature. Configuring the Make-Up Air unit to vary its speed to closely match
the blower speed of the external exhaust source blower motor allows for balanced system
operation.
Conforms to: UL STD.UL1995
Certified to: CSA STD.C22.2#236
DO NOT DESTROY THIS MANUAL. PLEASE READ CAREFULLY AND KEEP IN A SAFE
PLACE FOR FUTURE REFERENCE BY A SERVICE TECHNICIAN.
07/29/2019
Single or multi-speed exhaust blower interface
EI915

Advertisement

Table of Contents
loading

Summary of Contents for Electro Industries EM-MC00 Series

  • Page 1 --------------------------------------------------------------------------------------- Installation & Operating Manual --------------------------------------------------------------------------------------- Packaged Make-Up Air No Heat Models EM-MC00*, EM-MD00*, EM-ME00*, EM-MF00*, EM-MG00* Included With This Product  Permanent washable air filter  Powered inlet damper  (2) temperature sensors  (1) current transformer (CT doughnut) ...
  • Page 2: Table Of Contents

    Table of Contents Page Product Description Handling & Storage Placement & Mechanical Information Product Configurator (EC904) System Status Specification Table Dimensional Drawings Safety Consideration Installation Requirements Installation Overview Mechanical Installation Electrical Installation Control Wiring High Voltage Wiring Basic Setup & Configuration Software Configuration Understanding the Product Display Normal Operation Screens...
  • Page 3: Product Description

    Product Description This is a self-contained package with a permanent (washable) air filter, powered damper and blower. This product has been designed specifically for outside air inlet. All models (except EM-MB) include a multi-speed blower function; see Basic Setup & Configuration for further detail.
  • Page 4: Product Configurator (Ec904)

    System Status STATUS LED Status LED (front yellow LED) – is software driven LED which alerts the user that a message is available in the message center.  Status LED OFF = No message is available  Status LED Blinking = Message is available o To access available messages, the user must press and hold the “SELECT”...
  • Page 5: Specification Table

    Specification Table Volts Phase Max Fuse/ Internal Motor Motor Duct Model HACR Static Connection Amps EM-MC00-240-1-08 0.50” 240/208 1-50/60 Hz 1/10 8” EM-MD00-240-1-10 0.50” 240/208 1-50/60 Hz 10” EM-ME00-240-1-14 0.50” 240/208 1-50/60 Hz 14” EM-MF00-240-1-14 1050 0.50” 240/208 1-50/60 Hz 14”...
  • Page 6: Safety Consideration

    Hazards or unsafe practices could result in property damage, product damage, severe personal injury and/or death. 2. At Electro Industries the safety of the installer and the end user is of highest priority. Remember, safety is the installer’s responsibility and the installer must know this product well enough to instruct the end user on its safe use.
  • Page 7: Installation Overview

    Installation Overview This Make-Up Air unit contains interface/logic devices, one current transformer (CT doughnut), inlet and outlet temperature sensors, power open/power close damper, permanent washable filter and blower motor. Based on the application, other system components may be required to make your system operate as desired.
  • Page 8: Mechanical Installation

    Mechanical Installation This product is designed for zero clearance, but use the following mounting and spacing criteria: 1. Unit can be installed vertically or horizontally. When vertical, inlet must face down. 2. When using CT doughnut, use Class II low voltage wiring methods to connect CT to Make-Up Air unit.
  • Page 9 Horizontal installation – Ceiling Mount: Horizontal installation – Wall Mount: Option A: Cover Facing Down Option B: Cover Facing Side 07/29/2019 EI915...
  • Page 10 Vertical Installation – Wall Mount: 07/29/2019 EI915...
  • Page 11: Electrical Installation

    Electrical Installation Diagrams below represent general installation requirements. Due to various model sizes available, actual unit mechanical and wiring requirements will vary dependent upon specific model. Low Voltage Wiring Temperature Sensors Two temperature sensors are included, one used to sense inlet air temperature, the other to sense supply or outlet air temperature.
  • Page 12: Control Wiring

    Control Wiring There are two “tie-in” options available in connecting the Make-Up Air unit to a vent hood or other venting equipment.  Option 1 – Connect an isolated “dry” switch or relay contact to the R & W terminal block (TB1). ...
  • Page 13 High Voltage Vent Hood Lighting Note: For multi-speed vent hood installations, consideration must be made with vent hoods that include higher wattage lighting. It is possible that the low speed trigger point of the fan is equal to or lower than the current draw of the integrated lighting in the vent hood itself.
  • Page 14 4. Example – required three wraps, means the wire must go through the CT, loop back around, and then loop back around the second time through before it’s terminated at its original connection point. 5. The phasing or direction through the CT is not critical, simply one continuous wire. 6.
  • Page 15: High Voltage Wiring

    High Voltage Wiring Service Panel Circuit Breaker(s) Sizing – based upon unit size, the specification page shows appropriate service size requirements based on UL and NEC code. Note: Larger models include factory provided circuit breaker(s). This qualifies as a local disconnect at the product.
  • Page 16: Basic Setup & Configuration

    Basic Setup & Configuration Fahrenheit/Celsius Selection – Labeled “°F °C” (J22). This jumper allows for selection of degrees Fahrenheit or Celsius to be displayed on the display. NOTE: Factory default is °F. A power down reset is required upon changing of this jumper. Blower Speed Adjustment –...
  • Page 17: Software Configuration

    Software Configuration Software Setup Based on Specific Application – Multiple applications exist for this product. The unit is shipped preprogrammed for a range of applications with the ability to be reprogrammed to meet others. Below are the most prevalent applications. ...
  • Page 18: Understanding The Product Display

    Understanding the Product Display SELECT DISPLAY NEXT Scroll through available Select available onscreen options during installation options during field and setup. installation and setup. STATUS LED Indicates whether or not a message is available: Solid = No message available – status good Pulsing = Message available Note: If pulsing, press and hold select button.
  • Page 19: Normal Operation Screens

    Normal Operation Screens Under normal operating conditions, there are two screens that may be displayed based on system activity. Screen one – Idle screen – displayed when the unit is off. FAN OFF Screen two – Active screen – displayed when the unit is on. Inlet Air Temperature Outlet Air Temperature IN = 30°...
  • Page 20: Multi-Speed Setup

    Multi-Speed Setup If your application includes a multi-speed blower, follow the setup steps in this section. Enter into “MULTI-SPD SETUP” mode: Press and hold “SELECT” and “NEXT” for 5 seconds Step 1 FAN OFF Select “NEXT” to begin “MULTI-SPD SETUP” (select HOME to return) Step 2 MULTI-SPD...
  • Page 21 Set vent hood to medium speed “if applicable”, then press “NEXT” Step 5 SET EXT BL = MED PRESS NEXT If vent hood has a low speed select Y, if not select N Step 6 LO SPD Y  Set vent hood to low speed “if applicable”, then press “NEXT” Step 7 SET EXT BL = LO PRESS NEXT...
  • Page 22: Operational Indicators

    Operational Indicators LED Monitor Lights Green LED – is a representation of low voltage control power.  Green LED ON = good 24VAC power and fuse is in good working condition.  Green LED OFF = Fuse open or no 24VAC from transformer (or primary source breaker open).
  • Page 23: Start Up Inspection & Observations

     Included with this product is one CT. o Additional CTs are available. o Additional CTs can apply to any of the three terminal block pairs.  Use only Electro Industries’ CTs designed for this product (part #3629). 07/29/2019 EI915...
  • Page 24 External Damper, Field Furnished and Installed: Preparation or Pre-Wiring Sequence 1. Power up the Make-Up Air unit. 2. Jumper “R” and “W” screw terminal block (control board upper right). 3. Fan/blower will turn on and the internal damper will open. Observe the opening of the internal damper.
  • Page 25: Troubleshooting

    Troubleshooting NOTE PORTIONS OF TROUBLESHOOTING AND FOLLOWING FLOW CHART WILL NOT APPLY TO THESE NO HEAT MODELS. 1. This product contains several interference suppression components, but as an electronic logic product unpredictable and unusual transients or interferences may sometimes cause strange results.
  • Page 26 Troubleshooting Solution  This unit includes a 2A fuse located on the control board, verify it is Display is blank and nothing is turning on in good working condition.  If 2A fuse is open, replace.  If 2A fuse is not open, check the primary and secondary side of the transformer to ensure power is available.
  • Page 27: Routine Maintenance

    Troubleshooting Solution The blower is not turning on  Check unit display. Display should show “FAN OFF” or temperature screen.  If screen is blank, check 2A fuse.  If screen displays the “FAN OFF” screen, unit is not being told to turn on.
  • Page 28: Lcd Display

    07/29/2019 EI915...
  • Page 29 07/29/2019 EI915...
  • Page 30 07/29/2019 EI915...