Emerson Dixell XRB06CH Installing And Operating Instructions page 5

Digital controllers with energy saving management

Advertisement

Temperature
differential
for
Ft
activation of fans
FS
Fans stop temperature
Fn
Fan ON time
FF
Fan OFF time
FP
Probe selection for fan management
ALARMS
CA
Temperature alarm configuration
AU
Maximum temperature alarm
AL
Minimum temperature alarm
Differential
for
temperature
FH
recovery
Ad
Temperature alarm delay
dA
Exclusion of temperature alarm at startup
CONDENSER TEMPERATURE ALARMS
t2
Condenser alarm probe selection
L2
Condenser low temperature alarm
U2
Condenser high temperature alarm
Differential for condenser temperature
H2
alarm recovery
r1
Temperature alarm delay
Exclusion of temperature alarm after
r2
power-on
Compressor off due to condenser low
bL
temperature alarm
Condenser off due to condenser high
C2
temperature alarm
DEFROST-LIGHT RELAY
tb
Alarm relay muting
o1
First relay configuration
o2
Second relay configuration
o3 (*)
Third relay configuration
AP
Alarm relay polarity
ENERGY SAVING
Standard to ES mode time with door
Et
closed
ES to Standard mode time with door
St
closed
ES
Differential for energy saving
Door
open
time
before
do
Standard mode.
Overheating before activating super
1H
cooling function
1S
Sub Cooling
1t
Maximum duration for super cooling
Overheating before activating super
2H
cooling function
2S
Sub Cooling
LG
Light off in ES mode
DIGITAL INPUTS
iP
Digital input 1 polarity
2P
Digital input 2 polarity
iF
Digital input 1configuration
2F
Digital input 2 configuration
di
Digital input 1 alarm delay
2d
Digital input 2 alarm delay
Number of activation of the pressure
nS
switch
Compressor and fan status when open
dC
door
rd
Regulation with door open
Cd
Stop compressor delay
OTHER
bd
ECO key configuration (immediate)
bn
DOWN key configuration (immediate)
b3
ECO key configuration (timed)
b4
DOWN key configuration (timed)
d1
Thermostat probe display
d2
Evaporator probe display
d3
Third probe display
rS
Real SETPOINT value
rL
Firmware release
1592033060 - XRB06-07CH GB r1.0 12.02.2018.docx
forced
0 to 50°C; 0 to 90°F
-55 to 50°C; -67 to 99°F
0 to 15 min
0 to 15 min
nP; P1; P2; P3; P4
Ab; rE
ALL to 99°C; ALL to 99°F
-55°C to ALU; -67°F to ALU
alarm
0.1 to 25,5°C; 1 to 255°F
0 to 99 min
0 to 99 min
nP; P1; P2; P3; P4
-55 to 99°C; -67°F to 99°F
-55°C to 99°C; -67°F to 99°F
0.1 to 25°C; 1 to 45°F
0 to 99 min
0 to 99 min
n; Y
n; Y
n; Y
dF; Fn; AL; Li; AU; nF; dB; C2;
d2
dF; Fn; AL; Li; AU; nF; dB; C2;
d2
dF; Fn; AL; Li; AU; nF; dB; C2;
d2
CL; oP
0 to 99 hours
0 to 99 hours
-30 to 30°C; -54 to 54°F
restoring
0 to 255 sec
0.1 to 25.0°C; 1 to 45°F
0.1 to 25.0°C; 1 to 45°F
0 to 99 min
0.1 to 25.0°C; 1 to 45°F
0.1 to 25.0°C; 1 to 45°F
n; Y
CL; oP
CL; oP
do; ES; CP; EL; bA; dF; AU; HC;
Fn; PA; nu
do; ES; CP; EL; bA; dF; AU; HC;
Fn; PA; nu
0 to 99 min
0 to 99 min
0 to 15
no; Fn; cP; Fc
n; Y
0 to 15 min
dE; Li; AU; P2; ES
nu; OF; ES; dE
dE; Li; AU; P2; ES
nu; OF; ES; dE
Read Only
Read Only
Read Only
Read Only
Read Only
Pt
Parameter code table
0
50.0°C
(*) available only for XRB07CH
5
10
P2
Ab
99°C
-40°C
2.0
2
99
nP
-1.0°C
45°C
5°C
5
99
n
n
Y
Li
Fn
AL
CL
4
8
3
3
10
1.0
60
10
1.0
n
CL
CL
do
EL
2
2
15
Fn
Y
0
ES
nu
Li
oF
- - -
- - -
- - -
- - -
- - -
XRB06CH – XRB07CH
Read Only
- - -
5/5