13 USE THE HOT KEY
13.1
HOW TO PROGRAM THE HOT KEY FROM THE INSTRUMENT
(UPLOAD)
Program a controller by using the keypad.
1.
When the controller is ON, insert the "Hot Key" and push UP key.
2.
The "uP" message will appear, followed a by a flashing "Ed" label.
3.
Push SET key and the "Ed" will stop flashing.
4.
Turn OFF the instrument, remove the "Hot Key" and then turn it ON again.
NOTE: the "Er" message will be displayed in case of a failed programming operation. In this case push
the UP key if you want to restart the upload again or remove the "Hot Key" to abort the operation.
13.2
HOW TO PROGRAM AN INSTRUMENT USING HOT KEY
(DOWNLOAD)
1.
Turn OFF the controller.
2.
Insert a programmed "Hot Key" into the 5-PIN plug and then turn the controller ON.
3.
The parameter list present into the HOTKEY is automatically downloaded into the controller
memory. The "do" label will blink followed a by flashing "Ed".
4.
After 10 sec the controller restarts, loading the newer parameters.
5.
Remove the "Hot Key".
NOTE: the "Er" message is displayed in case of a failed copying operation. In this case turn the controller
off and then on again (if you want to retry the operation) or remove the "Hot Key" to end the operation.

14 ALARM SIGNALLING

Mess. Cause
P1
Room probe failure
P2
Evaporator probe failure
P3
Third probe failure
HA
Maximum temperature alarm
LA
Minimum temperature alarm
H2
Maximum temperature alarm for condenser
L2
Minimum temperature alarm for condenser
EA
External alarm
CA
Serious external alarm
PA
Pressure switch alarm
dA
Door Open
14.1
ALARM RECOVERY
Probe alarms P1, P2 and P3 starts some seconds after the fault in the related probe; they automatically
stop some seconds after the probe restarts normal operation. Check connections before replacing the
probe. Temperature alarms "HA", "LA", "U2" and "L2" automatically stop as soon as the temperature
returns to normal values.
Alarms "EA" and "CA" (with iF=bL) recover as soon as the digital input is disabled.

15 TECHNICAL DATA

Housing: self-extinguishing ABS
Case: frontal 32x74 mm; depth 60mm
Mounting: panel mounting in a 71x29mm panel cut-out
Protection: IP20
Frontal protection: IP65
Connections: Screw terminal block  2.5 mm
Power supply: (according to the model) 230Vac 10%, 50/60Hz; 110Vac 10%, 50/60Hz
Power absorption: 3.5VA max
Display: 2 digits, red LED, 14.2 mm high
Inputs: up to 3 NTC or PTC probes
Digital input: up to 2 free voltage contacts
Relay outputs:
Compressor: SPST 16(6) A 250Vac or 20(8) A 250Vac
Defrost: SPDT 8(3) A, 250Vac
AUX: SPST 8(3) A, 250Vac
Fan: SPST 5(2) A, 250Vac
Data storing: on the non-volatile memory (EEPROM)
Kind of action: 1B
Pollution degree: 2
Software class: A
Rated impulsive voltage: 2500V
Overvoltage Category: II
Operating temperature: 0T60°C (32T140°F)
Storage temperature: -25T60°C (-13T140°F)
Relative humidity: 20 to 85% (no condensing)
Measuring and regulation range:
NTC -40T110°C (-40T230°F)
PTC -40T150°C (-40T302°F)
Resolution: 0.1°C or 1°C or 1°F (selectable)
Accuracy (ambient temp. 25°C): ±0.1°C ±1 digit
1592033060 - XRB06-07CH GB r1.0 12.02.2018.docx
Outputs
Compressor output according to CY e Cn
Defrost end is timed
Outputs unchanged
Outputs unchanged
Outputs unchanged
Outputs unchanged
Outputs unchanged
Outputs unchanged
All outputs OFF
All outputs OFF
Depends on par. rd
2
wiring
16 CONNECTIONS
16.1
XRB06CH – 20+8+5A
16.2
XRB07CH – 16+8+8+5A

17 DEFAULT SETTING VALUES

LABEL
DESCRIPTION
REGULATION
HY
Differential in standard mode
HE
Differential in energy Saving mode
LS
Minimum Set Point value
US
Maximum Set Point value
ot
Thermostat probe calibration
P2
Evaporator probe presence
oE
Evaporator probe calibration
P3
Third probe presence
F3
Third probe calibration
od
Outputs activation delay at start up
AC
Anti-short cycle delay
CY
Compressor ON time faulty probe
Cn
Compressor OFF time faulty probe
DISPLAY
CF
Measurement units
rE
Resolution (only for °C)
Ld
Default Display
dy
Display delay
DEFROST
td
Defrost type
EA
Automatic defrost
PE
Defrost probe selection
dE
Defrost termination temperature
id
Interval between defrost cycles
Md
Maximum length for defrost
dd
Start defrost delay
dF
Display during defrost
Delay for temperature visualization after
tA
defrost
dt
Draining time
1d
Defrost enabled during super cooling
FANS
FC
Fans operating mode
Fd
Fans delay after defrost
XRB06CH – XRB07CH
RANGE
DEFAULT
0.1 to 25°C; 1 to 45°F
2.0°C
2.0°C
0.1 to 25°C; 1 to 45°F
-55°C to SET; -67°F to SET
-50.0°C
SET to 99°C; SET to 99°F
50.0°C
-9.9 to 9.9°C; -17 to 17°F
0.0
n; Y
n
-9.9 to 9.9°C; -17 to 17°F
0.0
n; Y
n
-9.9 to 9.9°C; -17 to 17°F
0.0
0 to 99 min
0
0 to 99 min
2
0 to 99 min
5
0 to 99 min
10
°C; °F
°C
dE; in
dE
P1; P2; P3; P4; SP; rt
P1
0 to 15 min
0
EL; in
EL
n; Y
n
nP; P1; P2; P3; P4
P2
-55 to 50°C; -67 to 99°F
8.0°C
0 to 99 hours
12
0 to 99 min
15
0 to 99 min
0
rt; in; SP; dF
dE
0 to 99 min
0
0 to 99 min
2
n; Y
n
cn; on; cY; oY
Cn
0 to 99 min
2
4/5