Digital controllers with energy saving management

Advertisement

ECO
(ECO) for light or energy saving mode activation/deactivation
(UP) In programming mode it browses the parameter codes or increases
the displayed value.
(DOWN/OFF) In programming mode it browses the parameter codes or
decreases the displayed value.
ONOFF
Keep it pressed for 3 sec for ON/OFF mode.
KEYS COMBINATION
+
To lock or unlock the keyboard
+
To enter in programming mode
+
To return to room temperature display
LED
MODE
On
Compressor running
Flashing
Anti-short cycle delay enabled (AC parameter).
ECO
On
Energy Saving mode active
On
Fans output enabled
Flashing
Fans delay after defrost
On
Measurement unit
Flashing
Programming mode
On
Measurement unit
Flashing
Programming mode
8.1
HOW TO SEE THE SET POINT
1.
Push and immediately release the SET key, the set point will be showed;
2.
Push and immediately release the SET key or wait for 3 sec to return to normal visualisation.
8.2
HOW TO CHANGE THE SETPOINT
1.
Push the SET key for more than 3 sec to change the Set point value;
2.
The value of the set point will be displayed and the "°C" or "°F" LED starts blinking;
3.
To change the Set value push the UP or DOWN arrows.
4.
To memorise the new set point value push the SET key again or wait for 10 sec.
8.3
HOW TO START A MANUAL DEFROST
A configurable button needs to be set as dE to activate the manual defrost control function. After that,
keep the DEF button pressed for the required time (immediate or 3 sec if timed) in order to activate a
defrost.
8.4
HOW TO CHANGE A PARAMETER VALUE
To change any parameter value, operate as follows:
1. Enter the Programming mode by pressing the SET+DOWN keys for 3 sec ("°C" or "°F" LED starts
blinking).
2. Select the required parameter. Press the SET key to display its value
3. Use UP or DOWN to change its value.
4. Press SET to store the new value and move to the following parameter.
To exit: Press SET+ UP or wait for 15 sec without pressing any key.
NOTE: the set value is stored even when the procedure is terminated by waiting for the time-out to
expire.
8.5
HIDDEN MENU
The hidden menu includes all the parameters of the instrument.
HOW TO ENTER THE HIDDEN MENU
1. Enter the Programming mode by pressing the SET+DOWN keys for 3 sec ("°C" or "°F" LED starts
blinking).
2. Released the keys and then push again the SET+DOWN keys for more than 7 sec. The "L2" label will
be displayed immediately followed from the Hy parameter.
NOW YOU ARE IN THE HIDDEN MENU.
3. Select the required parameter.
4. Press the SET key to display its value
5. Use UP or DOWN to change its value.
6. Press SET to store the new value and move to the following parameter.
To exit: Press SET+ UP or wait for 15 sec without pressing any key.
NOTE1: if there are no parameters in L1, after 3 sec the "nP" message will be displayed. Keep both keys
pushed till the "L2" message will be displayed.
NOTE2: the set value is stored even when the procedure is terminated by waiting for the time-out to
expire.
HOW TO MOVE A PARAMETER FROM THE HIDDEN MENU TO THE FIRST
LEVEL (AND VICEVERSA)
Each parameter present in the HIDDEN MENU can be removed or put into "THE FIRST LEVEL" (user
level) by pressing SET+DOWN. In HIDDEN MENU when a parameter is present in First Level the
decimal point is on.
8.6
TO LOCK THE KEYBOARD
1.
Keep pressed for more than 3 sec the UP and DOWN keys.
2.
The "OF" message will be displayed and the keyboard will be locked. If a key is pressed more
than 3 sec the "OF" message will be displayed.
8.7
TO UNLOCK THE KEYBOARD
Keep both UP and DOWN key pressed more than 3 sec until the "on" message will be displayed.
1592033060 - XRB06-07CH GB r1.0 12.02.2018.docx
SIGNIFICATO
9
PARAMETERS
REGULATION
HY
Differential in standard mode: (0.1 to 25°C; 1 to 45°F) differential for set point used in normal
mode. Compressor Cut IN is SET+HY. Compressor Cut OUT is when the temperature reaches
the set point SET.
HE
Differential in energy saving mode: (0.1 to 25°C; 1 to 45°F) differential for set point used in
energy saving mode. Compressor Cut IN is SET_ES+HE. Compressor Cut OUT is when the
temperature reaches the set point SET_ES.
LS
Minimum SET POINT: (-55°C to SET; -67°F to SET) sets the minimum value for the set point.
US
Maximum SET POINT: (SET to 99°C; SET to 99°F) set the maximum value for set point.
ot
First probe calibration: (-9.9 to 9.9°C; -17 to 17°F) allows to adjust possible offset of the first
probe.
P2
Evaporator probe presence: (n; Y) n=not present; Y=probe configured as present.
oE
Second probe calibration: (-9.9 to 9.9°C; -17 to 17°F) allows to adjust possible offset of the
second probe.
P3
Third probe presence: (n; Y) n=not present; Y=probe configured as present.
F3
Third probe calibration: (-9.9 to 9.9°C; -17 to 17°F) allows to adjust possible offset of the
second probe.
od
Outputs activation delay at start up: (0 to 99 min) this function is enabled at the initial start-
up of the instrument and inhibits any output activation for the period set in the parameter.
AC
Anti-short cycle delay: (0 to 99 min) minimum interval between the compressor stop and the
following restart.
CY
Compressor ON time with faulty probe: (0 to 99min) time during which the compressor is
active in case of faulty thermostat probe. With CY=0 compressor is always OFF.
Cn
Compressor OFF time with faulty probe: (0 to 99min) time during which the compressor is
OFF in case of faulty thermostat probe. With Cn=0 compressor is always active.
DISPLAY
CF
Measurement unit: (°C; °F) °C=Celsius; °F=Fahrenheit. WARNING: When the
measurement unit is changed the SET point and the values of the parameters Hy, LS, US, oE,
o1, AU, AL have to be checked and modified if necessary.
rE
Resolution (only for °C): (dE; in) dE=decimal between -9.9 and 9.9°C; in=integer.
Ld
Default display: (P1; P2; P3; P4; SP; dr) P1=thermostat probe; P2=evaporator probe;
P3=third probe; P4=not used; SP=Set point; dr=not used.
dy
Display delay: (0 to 99 min) when the temperature increases, the display is updated of 1°C
or 1°F after this time.
DEFROST
td
Defrost type: (EL; in) EL= electrical heater, compressor OFF; in=hot gas, compressor ON.
EA
Automatic defrost: (n; Y) n=function disabled; Y=a defrost is automatically activated at the
beginning of any energy saving period.
PE
Probe selection for first defrost: (nP; P1; P2; P3; P4) nP=not used, defrost ends by time;
P1=thermostat probe; P2=evaporator probe; P3=third probe; P4=not used.
dE
Defrost termination temperature: (-55 to 50°C; -67 to 99°F) if P2=Y, this is the temperature
measured by the evaporator probe which causes the end of defrost.
id
Interval between defrost cycles: (0 to 99 min) determines the time interval between two
consecutives defrosts cycles.
Md
Maximum duration for first defrost: (0 to 99min, 0 means no defrost) when P2=n, (no
evaporator probe present, the defrost is) it sets the defrost duration, when P2=y (defrost end
based on temperature) it sets the maximum length for defrost.
dd
Start defrosts delay: (0 to 99min) this is useful when different defrost start times are
necessary to avoid overloading the plant.
dF
Display during defrost: (rt; it; SP; dF) rt=real temperature; it=start defrost temperature;
SP=SET-POINT; dF=label dF.
tA
Delay for temperature visualization after defrost: 0 to 99 min.
dt
Drip time: (0 to 99min) time interval between reaching defrost termination temperature and
the restoring of the control's normal operation. This time allows the evaporator to eliminate
water drops that might have formed due to defrost.
FANS
FC
Fans operating mode: (cn, on, cY, oY) cn=in runs with the compressor, OFF during defrost;
on=continuous mode, OFF during defrost; cY=runs with the compressor, ON during defrost;
oY=continuous mode, ON during defrost.
Fd
Fans delay after defrost: (0 to 99 min) Interval between the end of a defrost operation and
the next evaporator fans start.
Ft
Temperature differential for forced activation of fans: 0 to 50°C; 0 to 90°F.
FS
Fans stop temperature: (-55 to 50°C; -67 to 99°F) setting of temperature, detected by
evaporator probe, above which fans are always OFF.
Fn
Fan ON time: (0 to 15 min) with FC=Cn or CY, (fan activated in parallel with compressor). It
sets the evaporator fan ON cycling time when the compressor is off. With Fn=0 and FF≠0 the
fan are always off, with Fn=0 and FF=0 the fan are always off.
FF
Fan OFF time: (0 to 15 min) with FC=Cn or CY, (fan activated in parallel with compressor). It
sets the evaporator fan off cycling time when the compressor is off. With Fn=0 and FF≠0 the
fan are always off, with Fn=0 and FF=0 the fan are always off.
FP
Probe selection for fan management: nP = fan regulator is disabled; P1 = thermostat probe;
P2 = evaporator probe; P3 =configurable probe; P4 = Probe on Hot Key plug.
ALARMS
CA
Temperature alarms configuration: (Ab; rE) Ab = absolute temperature: alarm temperature
is given by the AL or AU values. rE = temperature alarms are referred to the set point.
Temperature alarm is enabled when the temperature exceeds the SET+AU or SET-AL
values.
AU
Maximum temperature alarm: (AL to 99°C; AL to 99°F) when this temperature is reached
the alarm is enabled, after the Ad delay time.
AL
Minimum temperature alarm: (-55°C to AU; -67°F to AU) when this temperature is reached
the alarm is enabled, after the Ad delay time.
FH
Differential for temperature alarm recovery: (0.1 to 25.5°C; 1 to 45°F) differential for
temperature alarm recovery. It's also used for the restart of the fan when the FS temperature
is reached.