[ANG] analog output menu
Confi gurable
parameter
labels
ANT
ALO
AHI
Note:
(32)
Analog output
voltage 0-10 V
amperage 0-20 mA
amperage 4-20 mA
(33) it is possible to set an output range with AHI less than ALO to allow the output to
decrease with the increase of the measured parameter
[ADD] special parameters menu
Confi gurable
parameter
labels
DP0
TI0
DB0
IN0
DF0
DP1
TI1
DB1
IN1
DF1
Note:
(34) the parameter establishes in what way an output depends on a set-point or alarm
function. The values take on the following meanings:
0 output not active
1 output relative to set-point 1
2 output relative to set-point 2
3 change-over between output in direct (with set-point 1 and differential 1) and
output in reverse (with set-point 2 and differential 2) by means of digital input
(open - direct, closed - reverse).
Description
type of analog output
value corresponding
to lower limit
value corresponding
to upper limit
display reading
0-1
020
420
Description
output 1 dependency
on/off type or PWM 1
dead band 1
cut-in 1
logic 1 differential
output 2 dependency
on/off type or PWM 2
dead band 2
cut-in 2
logic 2 differential
- 48 -
User Manual – Thermoregulator FHT
Parameter
unit
value
default notes
min max
-
0
2
degrees -99 999
degrees -99 999
Parameter
unit
value
default notes
min max
-
0
10
-
0
1
-
0
1
%
-100 +100
%
-100 +100
-
0
10
-
0
1
-
0
1
%
-100 +100
%
-100 +100
0
(32)
00.0
(33)
100
(33)
(34)
(35)
(36)
(37)
(38)
(34)
(35)
(36)
(37)
(38)