COOLING PERFORMANCES – Model X 1100 AR ............COOLING PERFORMANCES – Model X 1900 AR ............COOLING PERFORMANCES – Wasted water – Model X 1100 AO ....... COOLING PERFORMANCES – Wasted water – Model X 1900 AO ........ COOLING PERFORMANCES – Recycled water – Models X 1100/X 1900 AO ....
INTRODUCTION " When the HCFC fluids are replaced, these appliance have been optimized to operate with the R-407C coolant which contains no chlorine and has no effect on the ozone layer." 1. DEFINITION • Electrical, water and refrigerant pipe connections on the right or left side.
Page 4
· AR Model 3.6 Control / Regulation – Reserve liquid receiver. • Fascia grouping the controls (Main “ON/OFF” switch – Thermostatic pressure reducer with pressure with control light – Heating “ON/OFF” and Cooling balancing. “ON/OFF”) and the regulation (inverting thermos- –...
X 1100/X 1900 TH 3052 COOLING PERFORMANCES Model X 1100 AR AIR FLOW : 2000 m³/h Air temperature Air temperature at condenser inlet (°C) at evaporator inlet (°C) 10028 9664 9300 8937 8573 8209 7845 3215 3410 3605 3799 3994 4189 4384 6192...
TH 3053 X 1100/X 1900 COOLING PERFORMANCES Model X 1900 AR AIR FLOW : 3200 m³/h Air temperature Air temperature at condenser inlet (°C) at evaporator inlet (°C) 16748 16140 15533 14925 14318 13710 13103 5301 5622 5943 6264 6585 6906 7228 10448 10675 10903 11130 11357 11584...
X 1100/X 1900 TH 3054 COOLING PERFORMANCES Wasted water • Model X 1100 AO NOMINAL AIR FLOW Qn : 2000 m³/h Air temperature at evaporator Wasted water supply inlet (°C) Water temperature °C 10372 Water consumption 3246 Water pressure 7063...
X 1100/X 1900 TH 3055 COOLING PERFORMANCES Wasted water • Model X 1900 AO NOMINAL AIR FLOW Qn : 3200 m³/h Air temperature at evaporator Waste water supply inlet (°C) Water temperature °C 15910 Water consumption 1135 5205 Water pressure 10994 12585 14176...
X 1100/X 1900 TH 3056 COOLING PERFORMANCES Recycled water • Models X 1100 /X 1900 AO Recycled water supply Air temperature at evaporator X1100 X1900 inlet (°C) Inlet water temperature °C Water pressure BH BS X1100 X1900 Water consumption 2100 3050 10372 15910...
TH 3057 X 1100/X 1900 AERAULIC CHARACTERISTICS Models AR/AO FRONT AND REAR AIR INTAKE WITH CLEAN AIR FILTER Model X 1100 Model X 1900 Air flow Air flow Example : Exemple : Model X 1100 - Qa = 1800 m Model X 1900 - Qa = 2700 m Standard ventilation (VS) with high rotation speed (GV) Standard ventilation (VS) with normal rotation speed (GV)
X 1100/X 1900 TH 3058 HYDRAULIC CHARACTERISTICS Model AO - Condenser supply HYDRAULIC PRESSURE LOSS WITH PRESSOSTAT VALVE (AV) WITHOUT PRESSOSTAT VALVE (SV) ∆Pw (kPa) Qw (m Air flow AV = WITH valve (for wasted water) Nominal SV = WITHOUT valve 100 kPa = 1 bar flow (for recycled water)
TH 3059 X 1100/X 1900 HEATING PERFORMANCE HOT WATER COIL Models AR/AO (Accessory) Model X 1900 Ex : Tsi = 20 °C X 1100 Water = 90/80 °C Twm = 85 °C X 1900 =29,7 kW = Total cooling capacity with nominal air flow C..ICIENT WATER FLOW Pt = K...
X 1100/X 1900 TH 3060 ELECTRICAL HEATER / HOT WATER COIL ACCESSORIES IN-BUILT HEATER INTAKE DISCHARGE Marks Models X 1100 X 1900 Nominal power input 15,5 29,7 Nominal water flow HOT WATER Water pressure loss COIL Ø Connections M 26 x 34 Total power input ELECTRICAL Number of stages...
Page 15
TH 3061 X 1100/X 1900 CONTROLS AND REGULATION Control panel Ventilation On/Off switch NOTES : O Off With the automatic “Cooling/ 1 On (with control light) Heating” thermostat with "Cooling" selection switch neutral zone supplied with the O Off integrated electric heater, 1 On "Cooling"...
X 1100/X 1900 TH 3062 DESCRIPTION OF THE AIR TREATMENT UNIT Discharge plenum (accessory) with double deflection Access panel to the fan assembly and the hot water coil (accessory) Control panel Hot water coil connections and bleed. Access on the right and left side Air intake grille Connection for fresh air intake (accessory) on the right, left or rear...
TH 3063 X 1100/X 1900 DIMENSIONS • INSTALLATION Air treatment unit Dimensions in mm See exact mounting specifications in the installation instructions supplied with the material. Models REAR VIEW FRONT VIEW X 1100 X 1900 1540 1735 1000 TOP VIEW (whithout plenum) CLEARANCES(mm) REAR .RONT...
X 1100/X 1900 TH 3064 DIMENSIONS • INSTALLATION Outdoor condensing unit - Type UC 33A/UC 53A Model AR Dimensions in mm Electrical compartment access panel INTAKE DISCHARGE CLEARANCES FLOOR MOUNTING AND FIXING 7+!!) 7+#!) Top : 2,50 m Air flow 3700 5000 Rotational speed ventilation...
TH 3065 X 1100/X 1900 REFRIGERATION PIPEWORK Model AR UC 33A UC 53A CONDENSING UNIT A – Discharge line B – Liquid line CONDENSER AT THE SAME LEVEL AS THE INDOOR UNIT INDOOR UNIT L maxi. = 45 m CONDENSER Bending of refrigeration pipes : R ≥...
Page 20
X 1100/X 1900 TH 3066 ELECTRICAL CONNECTIONS Main power supply POWER SUPPLY POWER SUPPLY POWER SUPPLY 3 ~ 230 V + Earth 3 N ~ 400 V + Earth 3 ~ 400 V +Earth (regulated in France) (with neutral) (without neutral) 3~230 V - 50 Hz 3~400 V - 50 Hz 3~400 V - 50 Hz...
Page 21
TH 3067 X 1100/X 1900 ELECTRICAL SPECIFICATIONS Main power supply Unit type Model X 1100 Model X 1900 Power supply 3 ~230 V* - 50 Hz 3N ~400 V - 50 Hz 3 ~230 V* - 50 Hz 3N ~400 V - 50 Hz Models ...
Page 22