Novus NP600 Instruction Manual

Novus NP600 Instruction Manual

Relative pressure transmitter

Advertisement

Quick Links

NP600
RELATIVE PRESSURE TRANSMITTER – INSTRUCTIONS MANUAL – V1.0x D
PRESENTATION
The NP600 relative pressure transmitter series are robust and
reliable equipment suitable for general industrial applications. Its
great advantage is the possibility of a fast and easy configuration of
the operating range. With the aid of a software, the user has access
to the most important information of the transmitter and can set the
most appropriate configuration for the process.
The NP600 model has a ceramic sensor with high mechanical
stability.
PRECAUTION
Before operating the transmitter, carefully read its specifications and
operating instructions. In case of damage caused by incorrect
operation or inappropriate usage, and its consequences, the
guarantee becomes ineffective and null.
A specialized professional shall perform the installation.
A specific electrical power supply network should be provided for
instruments use only.
UNPACKING
After unpacking the product, besides the transmitter it must be
available:
A quick guide to installation and operation.
A sealed electrical connector.
A screw to adjust the transmitter and the connector.
IDENTIFICATION
An identification label is attached to the equipment housing. On this
label, you can found detailed information about the transmitter.
Fig. 1 shows the identification label with their respective information.
Fig. 1 – Transmitter identification
NOVUS AUTOMATION.
SPECIFICATIONS
Maximum Range (Max. Range):
0-2 / 0-5 / 0-10 / 0-20 / 0-50 / 0-100 Bar (*)
Rangeability:
3:1
Measurement Accuracy:
≤ 50 bar ...................................................... < ±0.5 % Max. Range
100 bar ....................................................... < ±1.0 % Max. Range
Including linearity, hysteresis and repeatability, 25 °C
Thermal Maximum Deviation:
< ±0.06 % Max. Range / °C
Overpressure Range:
Twice the value specified for the Maximum Measurement Range
Output Signal (Output):
Electric currente, 4-20 mA, 2 wires.
Power Supply (Power):
11 to 33 Vdc
Electrical Connection:
Connector for Type A valves (DIN EN 175301-803), IP65.
Conductor 1.5 mm² (max.) and cables between 6 and 8 mm in
diameter.
Operating temperature:
-20 to 70 °C
Dinamic Response:
< 30 ms
Process Conection (Thread):
¼ NPT, ½ NPT, ½ BSP, G ¼ (*)
Materials:
Metal housing of the transmitter ...................................... Stainless 316
Sensor (NP600) .................................................. Ceramic (Al
Wetted parts (NP600) ............................ Sensor Ceramic (Al
.................................................................................. Sealing ring, FKM
................................................... Metal connection, stainless steel 316
Compatibility: Any gas or liquid compatible with the constituent
materials of the wetted parts.
(*)Information available on the product identification label.
O
96 %)
2
3
O
96 %)
2
3
1/3

Advertisement

loading
Need help?

Need help?

Do you have a question about the NP600 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Novus NP600

  • Page 1 Measurement Accuracy: The NP600 model has a ceramic sensor with high mechanical ≤ 50 bar ............< ±0.5 % Max. Range stability.
  • Page 2 When a new configuration is required, you should use the setting fields. Transmitter Configuration Kit. This kit includes the TxConfig-II software, distributed free on the Novus website, and the TxConfig- 3. Measuring Range: USB-DIN43650 interface, which can be purchased in our distribution Setting the measurement range assumed by the transmitter.
  • Page 3 NP600 Pressure Transmitter DIMENSIONS Fig. 5 – Transmitter dimensions THREAD A (mm) B (mm) WEIGHT (g) NPT ¼ 15.5 46.5 NPT ½ 20.0 51.0 BSP ½ 14.0 45.0 G ¼ 14.0 45.0 Table 1 – Dimensions WARRANTY Warranty conditions available website www.novusautomation.com/warranty.