COMBUSTION ADJUSTMENTS

G20
CO2 emission
Gaz Consumption
Flue gas mass flow
10.1

EMISSION SETPOINTS

WALLCON X-treme boilers are offer to sale after all required
combusiton, efficiecny and safety controls. Emission settings
mustn't be changed which are made by GASSERO. However,
if there is a deviation in the values which are given below,
emission settings should be changed by GASSERO
authorized service.
Wallcon X-treme
42
min.
8,9
%
0,94
m3 /h
3,00
g/sec.
A
– Nominal gas flow adjustment screw
B
– Burner gas inlet measurement point
C
– Main gas inlet measurement point
D
– Minimum gas flow adjustment screw
34
These combution settings mentioned below must
be issued by authorized GASSERO services.
Flue gas analyzer must be used during to the
combustion adjustments.
Wallcon X-treme
50
max.
min.
max.
9,1
9
9,3
3,86
0,94
4,85
17,00
4,00
21,00
Wallcon X-treme
67
min.
max.
8,6
9,1
1,31
6,43
5,00
28,00

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wallcon x-treme 50Wallcon x-treme 42

Table of Contents