IB IL 24 AI 2/SF-230
Safety Devices
Surge voltage
Electrical Isolation/Isolation of the Voltage Areas
To provide electrical isolation between the logic level and the I/O area it is necessary to
supply the bus terminal and the sensors, which are connected to the anaolg input terminal
described in this data sheet, from separate power supplies. Interconnection of the 24 V
power supplies is not permitted.
Common Potentials
24 V main power, 24 V segment voltage, and GND have the same potential. FE is a separate
potential area.
Separate Potentials in the System Consisting of Bus Terminal/Power Terminal and I/O
Terminal
- Test Distance
5 V supply incoming remote bus/7.5 V supply (bus logic)
5 V supply outgoing remote bus/7.5 V supply (bus logic)
7.5 V supply (bus logic)/24 V supply U
7.5 V supply (bus logic)/24 V supply U
I/Os/functional earth ground
Error Messages to the Higher-Level Control or Computer System
Failure of the internal voltage supply
I/O error/user error
30
Suppressor diodes in the analog inputs
/ I/O
ANA
/functional earth ground
ANA
Yes
Yes, error message through the process data
input words (see page 14)
- Test Voltage
500 V AC, 50 Hz, 1 min
500 V AC, 50 Hz, 1 min
500 V AC, 50 Hz, 1 min
500 V AC, 50 Hz, 1 min
500 V AC, 50 Hz, 1 min