Phoenix Contact IB IL 24 AI 2/SF-230 User Manual page 21

Interbus inline terminal with two analog input channels
Table of Contents

Advertisement

Measuring range -20 mA through +20 mA/-10 V through +10 V
Input Data Word
(Two's Complement)
hex
7FFF
7FF7
4000
0001
0000
FFFF
8001
8000
Measuring range 4 mA through 20 mA
Input Data Word
(Two's Complement)
hex
7FFF
7FFE
4000
0001
0000
0000
7FFF
6232A
-20 mA Through +20 mA
I
Input
mA
≥ +19.999389
+19.998779
+10.0
+0.61035 µA
0
-0.61035 µA
-19.999389
≤ -20.0
4 mA Through 20 mA
I
Input
mA
≥ 19.9995116
19.9990232
12.0
0.4884 µA
4.0
3.2 through 4.0
< 3.2
IB IL 24 AI 2/SF-230
-10 V Through +10 V
U
Input
V
≥ +9.999939
+9.99939
+5.0
+305.0 µV
0
-305.0 µV
-9.99939
≤ -10.0
21

Advertisement

Table of Contents
loading

Table of Contents