Measuring range 0 V through 10 V
Input Data Word
(Two's Complement)
hex
dec
8001
Overrange
2A55
10837
2710
10000
0001
1
0000
0
Measuring range -10 V through +10 V
Input Data Word
(Two's Complement)
hex
dec
8001
Overrange
2A55
10837
2710
10000
0001
1
0000
0
FFFF
-1
D8F0
-10000
D5A6
-10837
8080
Below range
6232A
0 V Through 10 V
U
Input
V
> +10.837
+10.837
+10.0
+0.001
0
-10 V Through
+10 V
U
Input
V
> +10.837
+10.837
+10.0
+0.001
0
-0.001
-10.0
-10.837
<-10.837
Measuring range 0 mA through 20 mA
Input Data Word
(Two's
Complement)
hex
dec
8001
Overrange
54AA
21674
4E20
20000
0001
1
0000
0
Measuring range -20 mA through +20 mA
Input Data Word
(Two's Complement)
hex
dec
8001
Overrange
54AA
21674
4E20
20000
0001
1
0000
0
FFFF
-1
B1E0
-20000
A656
-21674
8080
Below range
IB IL 24 AI 2/SF-230
0 mA Through 20 mA
I
Input
mA
> +21.674
+21.674
+20.0
+0.001
0
-20 mA Through
+20 mA
I
Input
mA
> +21.674
+21.674
+20.0
+0.001
0
-0.001
-20.0
-21.674
<-21.674