Setting cooling set point, St1:
1. Press "SET" and display should show St1 and then the pre-set value of St1. (default: +35°C / +95°F)
2. Reach the desired value by using ▲ or ▼.
3. Press "SET" again to save the new value of St1.
Setting heating set point, St2 (only for units supplied with internal heater):
1. Press "SET" twice slowly and display should show St2 and then the pre-set value of St2. (default: +5°C /
+41°F)
2. Reach the desired value by using ▲ or ▼.
3. Press "SET" again to save the new value of St2.
​ S etting temperature units (°C / °F), low temperature alarm and high temperature alarm:
1. Press "PRG" button for 5 seconds to reach the modifiable parameter list.
2. Use ▲ or ▼ to reach the desired parameter:
C18 for temperature unit of measure
°C = 0
°F = 1
P25 for low temperature alarm threshold (default -10°C / +14°F)
P26 for high temperature alarm threshold (default +55°C / +131°F)
3. Press "SET" on the desired parameter to display the current value.
4. Use ▲ or ▼ to reach the desired value.
5. Pressing "SET" temporarily saves the new value and returns to the parameters list.
6. Repeat steps 2-5 to set other parameters.
7. Press "PRG" for 5 seconds to permanently save the new values.
Version Nr. 1-5 - 03.09.2019
Doc. Nr. 9957081182SG