Taking Into Operation; Trouble Shooting; Maintenance & Cleaning - SCE -AC2550B120VSS Manual

Table of Contents

Advertisement

Attention!
The unit can be damaged by lack of lubricant. To ensure that the compressor is adequately lubricated the oil,
which has been displaced during transport, must be allowed to flow back into it. The unit must therefore be
allowed to stand for at least 30 min. before being connected to the mains and taken into operation.
The unit / system must be protected with a MCB Type D or K.
Upon connection the internal fan will start working. If the temperature inside the enclosure is higher than the
set value of the controller both the compressor and external air fan start working. Once the air inside the
enclosure reaches the set temperature the compressor and external fan will stop.
The unit is pre-set at 35°C, which is suitable for most of the electronic devices.
Failure
Condition
Internal fan does not work
Internal fan works, external fan
Unit
and compressor don't work
doesn't
cool
Internal fan works, external fan
and compressor don't work.
Display shows alternating OFF
and temperature
External and internal fan work,
Unit
compressor does not work
doesn't
cool
Compressor works, external fan
doesn't work
Compressor and fans (external
and internal) work all the time
Enclosure
temperature
Compressor and external fan
too hot
work in alternating mode
(ON / OFF)
Enclosure door open
Excessive
condensate
Enclosure door closed
Always switch power supply off before starting any maintenance on
the unit.
The cooling unit is generally maintenance free and can be operated without filters in most environments. For
units with filters these should be checked, cleaned and if necessary replaced on a regular basis. In addition the
unit should have regular functional tests (approx. every 2,000 hours depending on the grade of ambient
pollution).
Disposal.
The cooling unit contains R134a refrigerant and small quantities of lubricating oil. Replacement, repairs and
final disposal must be done according to the regulations of each country for these substances.
Version Nr. 1-5 - 03.09.2019

12. Taking into operation

13. Trouble shooting

Cause
Power not connected.
Enclosure temperature is below
setting temperature (St)
Door switch contact is open
Controller doesn't work
The sequence of the phases
inside the power supply
connector is incorrect
Compressor motor electrical
failure
Capacitor for compressor failed Replace capacitor
External fan needs to be
replaced
Cooling unit undersized
Thermal compressor protector
triggered
Refrigerant leakage
Ambient air gets into the
enclosure
Enclosure IP protection class
is below IP54
Damaged or misplaced sealing
strip
14. Maintenance & Cleaning
Doc. Nr. 9957081182SG
Solution
Verify power supply
Verify values of parameter
"St"
Verify door switch
Replace controller
Change phases inside power
supply connector
Have compressor replaced
by qualified service technician
Replace external fan
Enclosure needs a cooling
unit with with higher capacity
Verify if ambient temperature
is too high,clean condenser
Contact dealer/service center
Ensure door is closed, add
a door switch and connect
it to controller
Seal all openings of the
enclosure
Repair sealing strip
accordingly
14 / 15