6.2.4 Installing a Bottom-discharge Grille for 4-ton and 5-ton Models
The optional, bottom-discharge grille is a 3-way louvered-air grille, painted white, and added to a T-bar
grid assembly for air discharge directly into room from the bottom of the unit. Use a separate filter-box kit
for filtration and connection to field-provided room-air-return ductwork.

6.2.5 Guidelines for Ducted Systems

Observe the following for all ductwork.
Ductwork should be fabricated and installed in accordance with local and national codes.
Use flexible ductwork or nonflammable cloth collars to attach ductwork to the unit and to
control vibration transmission to the building.
Attach the ductwork to the unit using the flanges provided. Locate the unit and ductwork so
that the discharge air does not short-circuit to the return-air inlet.
Ductwork that runs through a conditioned space or is exposed to areas where condensation
may occur must be insulated. Insulation of ductwork is vital to prevent condensation during
the cooling cycle.
The use of a vapor barrier is required to prevent absorption of moisture from the surrounding
air into the insulation.
If the return-air duct is short or if noise is likely to be a problem, sound-absorbing insulation
should be used inside the duct.
Ductwork should be suspended using flexible hangers. Ductwork should not be fastened
directly to the building structure.