Appliance Application Requirements - Carrier 140/E Series Installation, Start--Up, Operating, And Service And Maintenance

Table of Contents

Advertisement

The Chinmey Adapter Kit is a listed alternative venting system
for these furnaces. See the kit instructions for complete details.
This furnace is pernfitted to be vented into a clay tile-lined
masonry chinmey that is exposed to the outdoors below the roof
line, provided:
1. Vent connector is Type-B double-wall,
and
2. This furnace is common vented with at least 1 draft hood-
equipped appliance, and
3. The combined appliance input rating is less than the max-
imum capacity given in Table 8, and
4. The input rating of each space heating appliance is greater
than the minimum input rating given in Table 9 for the
local 99% Winter Design Temperature. Chinmeys having
internal areas greater than 38 in2 (24516 mm2)require fur-
nace input ratings greater than the input ratings of these
furnaces. See footnote at bottom of Table 9, and
5. The authority having jurisdiction approves.
If all of these conditions
cannot be met, an alternative venting
design shall be used, such as the listed chinmey adapter kit with a
furnace listed for use with the kit, a listed chinmey-lining
system,
or a Type-B common vent.
Inspections before the sale and at the time of installation will
deternfine the acceptability of the chinmey or the need for repair
and/or
(re)lining.
Refer to Fig. 34 to perform
a chinmey
inspection.
If the inspection
of a previously
used tile-lined
chinmey:
a. Shows signs of vent gas condensation,
the chinmey
should be relined in accordance with local codes and the
authority having jurisdiction. The chinmey should be re-
lined with a listed metal liner, Type-B vent, or a listed
chinmey adapter kit shall be used to reduce condensation.
If a condensate drain is required by local code, refer to
the NFPA 54 /ANSI Z223.1-2009,
Section 12.10 for ad-
ditional information on condensate drains.
b. Indicates the chinmey exceeds the maximum pernfissible
size in the tables, the chinmey should be rebuilt or relined
to conform to the requirements of the equipment being
installed and the authority having jurisdiction.
A chinmey without a clay tile liner, which is otherwise in good
condition, shall be rebuilt to conform to ANSI/NFPA 211 or be
lined with a UL listed metal liner or UL listed Type-B vent.
Relining with a listed metal liner or Type-B vent is considered to
be a vent-in-a-chase.
If a metal liner or Type-B vent is used to line a chinmey, no other
appliance shall be vented into the annular space between the
chinmey and the metal liner.
Exterior Masonry
Chimney FAN + NAT
Installations
with Type-B Double-Wall
Vent
Connectors
©NFPA & AGA
Table
8 - Combined
Appliance
Maximum
Input
Rating
in
Thousands
of BTUH
per Hour
INTERNAL AREA OF CHIMNEY
VENT HEIGHT
FT. (M)
5 (1.8)
8 (2.4)
10 (6.)
15 (4.5)
20 (6.0)
30 (9.1)
SO. IN. (SO. MM)
12
19
28
38
(7741)
(12258)
(18084)
(24518)
74
119
178
257
80
130
193
279
84
168
207
299
N R
152
233
334
N R
N R
250
668
NR
NR
NR
404
Table 9 - Minimum
Allowable
Input
Rating
of Space-Heat-
ing Appliance
in Thousands
of BTUH
per Hour
VENT HEIGHT
(FT)
INTERNAL AREA OF CHIMNEY
SQ. IN. (SQ. aM)
12
19
28
38
(7741)
(12258)
(18084)
(24518)
Local
99% Winter
Design
Temperature:
17 to 28°F
(-8
to -3°C)
6 (1.8)
0
55
99
141
8 (2.4)
52
74
111
154
10 (6.0)
NR
90
125
169
15 (4.6)
NR
NR
167
212
20 (6.1)
NR
NR
212
258
30 (9.1)
NR
NR
NR
362
Local
99% Winter
Design
Temperature:
5 to 18°F * (-15
to -9°C)
6 (1.8)
NR
78
121
166
8 (2.4)
NR
94
165
182
10 (6.0)
NR
111
149
198
15 (4.6)
NR
NR
196
247
20 (6.1)
NR
NR
NR
293
30 (9.1)
NR
NR
NR
377
Local
99% Winter
Design
Temperature:
-10
to 4°F * (-23
to -18°C)
6 (1.8)
NR
NR
145
196
8 (2.4)
NR
NR
159
216
10 (6.0)
NR
NR
175
261
15 (4.6)
NR
NR
NR
286
20 (6.1)
NR
NR
NR
333
30 (9.1)
NR
NR
NR
NR
Local
99% Winter
Design
Temperature:
-11
°F (-24°C)
or lower
Not recommended
for any vent configuration.
*The 99.6% heating db temperatures
found in the 1997 or 2001 ASHRAE
Fundamentals
Handbook,
Climatic Design Information
chapter, Table 1A
(United States) or the 2005 ASHRAE Fundamentals
handbook,
Climatic
Design Information
chapter, and the CD-ROM
included
with the 2005
ASHRAE Fundamentals
Handbook.
APPLIANCE
APPLICATION
REQUIREMENTS
Appliance operation has a significant impact on the performance
of the venting system. If the appliances are sized, installed,
adjusted, and operated properly, the venting system and/or the
appliances should not suffer from condensation
and corrosion.
The venting system and all appliances shall be installed in
accordance with applicable listings, standards, and codes.
The furnace should be sized to provide
100% of the design
heating load requirement plus any margin that occurs because of
furnace model size capacity increments. Heating load estimates
can be made using
approved
methods
available from
Air
Conditioning
Contractors
of America
(Manual
J); American
Society
of
Heating,
Refrigerating,
and
Air-Conditioning
Engineers; or other approved engineering
methods. Excessive
over-sizing of the furnace could cause the furnace and/or vent to
fail prematurely. When a metal vent or metal liner is used, the
vent must be in good condition and be installed in accordance
with the vent manufacturer's instructions.
To prevent condensation
in the furnace and vent system, the
following precautions must be observed:
1. The return-air temperature must be at least 60°F (15°C)
db except for brief periods of time during warm-up from
setback at no lower than 55°F (13°C) db or during initial
start-up from a standby condition.
28

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents