Table of Contents

Advertisement

Gas piping
nmst
be installed
in accordance
with
national
and
local codes. Refer to current edition
of NFGC
in the U.S.
NOMINAL
IRON
PIPE
SIZE
IN. (MM)
1/2 (12.7)
3/4 (19.0)
1 (25.4)
1-1/4
(31.8)
1-1/2
(38.1)
Table 6 - Maximum
Capacity
of Pipe
INTERNAL
LENGTH OF PIPE - FT. (M)
DIA.
10
20
30
40
50
IN. (MM)
(3.0)
(6.0)
(9.1)
(12.1)
(15.2)
0.622
(158)
175
120
97
82
73
0.824
(20.9)
360
250
200
170
151
1.049
(26.6)
680
465
375
320
285
1.380
(35.0)
1400
950
770
660
580
1.610
(40.9)
2100
1460
1180
990
900
Cubic ft. of natural gas per hr for gas pressures of 0.5 psig (14-In.
W.C.)
or less and a pressure drop of 0.5-In.
W.C. (based on a 0.60 specific
gravity gas). Ref: Table 6 and NFPA54/ANSI
Z223.1-2009.
Installations
nmst
be
made
in accordance
with
all authorities
having
jurisdiction.
If possible,
the gas supply
line should
be a
separate
line running
directly
from meter to furnace.
NOTE:
In the state of Massachusetts:
1. Gas supply
connections
MUST
be performed
by a li-
censed plumber
or gas fitter.
2. When
flexible
connectors
are used, the maximum
length
shall not exceed
36 inches (915 ram).
3. When lever handle type manual
equipment
shutoff valves
are used, they shall be T-handle
valves.
4. The use of copper
tubing
for gas piping is NOT approved
by the state of Massachusetts.
Refer to Table 6 for recommended
gas pipe sizing.
Risers nmst be
used to connect
to furnace
and to meter. Support
all gas piping
with appropriate
straps, hangers,
etc. Use a minimum
of 1 hanger
every
6 ft.
(1.8
M). Joint
compound
(pipe
dope)
should
be
applied
sparingly
and only
to male threads
of joints.
Pipe dope
must be resistant
to the action of propane
gas.
FIRE
OR EXPLOSION
HAZARD
Failure
to follow
this warning
could
result
in personal
iniury,
death, and/or property
damage.
If local
codes
allow
the
use of a flexible
gas appliance
connector,
always
use a new listed connector.
Do not use a
connector
which
has
previously
served
another
gas
appliance.
Black
iron pipe shall be installed
at the furnace
gas control
valve and extend
a n_ininmm
of 2 in. (51 ram)
outside
the furnace.
An
accessible
manual
equipment
shutoff
valve
MUST
be
installed
external
to furnace
casing and within 6 ft. of furnace.
A
l/8-in.
(3 ram) NPT
plugged
tapping,
accessible
for test gauge
connection,
MUST
be
installed
immediately
upstream
of gas
supply
connection
to
furnace
and
downstream
of
manual
equipment
shutoff valve.
NOTE:
The
furnace
gas
control
valve
inlet
pressure
tap
connection
is suitable
to use as test gauge connection
providing
test pressure
DOES
NOT
exceed
maximum
0.5 psig
(14-In.
W.C.)
stated
on
gas
control
valve.
(See
Fig.
48.)
Some
installations
require gas entry on right side of furnace
(as viewed
in upflow).
(See Fig. 21.)
TOP VIEW
OF BURNER
AND MANIFOLD
ASSEMBLY
90 ° Elbow
2"(51mm)
Nipple
Supply
g
Street Elbow
L
Gas Valve
Fig. 21 - Burner
and Manifold
A08551
Install a sediment
trap in riser leading
to furnace
as shown
in Fig.
22. Connect
a capped nipple
into lower end of tee. Capped
nipple
should extend below level of furnace
gas controls.
Place a ground
joint
union
between
furnace
gas
control
valve
manifold
and
exterior
manual
equipment
gas shutoff valve.
GAS
SUPPLY
/_
MANUAL _/
II
SHUTOFF
_
_
VALVE
(REQUI RED)j_'_,
SEDIMENT--
[
TRAP
/
UNION .--,r
Fig. 22 - Typical
Gas Pipe Arrangement
A02035
FURNACE
DAMAGE
HAZARD
Failure to follow
this caution
may result in furnace
damage.
Connect
gas
pipe
to furnace
using
a backup
wrench
to
avoid damaging
gas controls
and burner
misalignment.
19

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents