Carrier 140/E Series Installation, Start--Up, Operating, And Service And Maintenance page 15

Table of Contents

Advertisement

LINE CONTACT
ONLY P ERMISSIBLE
BETWEEN
LINES FORMED
BY INTERSECTIONS
OF
THE TOP AND TWO SIDES O F THE FURNACE
JACKET
AND BUILDING
JOISTS,
STUDS,
OR FRAMING.
17
3/4"
(451 mm)OVERALL
4
3/4"
(121mm) UNDER DOOR
1" (25mm) UNDER
FURNACE
ENTRY
VENT
EXTEND
OUT 12" (305mm)
FROM FACE OF DOOR
_0-1N. (762mm)
MIN WORK AREA *WHEN
USED WITH
SINGLE WALL VENT
CONNECTIONS
EQUIPMENT
MANUAL
SHUT-OFF GAS VALVE
SEDIMENT
TRAP
UNION
A10164
Fig. 17 - Typical
Attic Installation
Not
all horizontal
furnaces
are
approved
for
side
return
air
connections.
(See Fig. 20.)
FILTER
ARRANGEMENT
CARBON
MONOXIDE
POISONING
HAZARD
Failure
to follow
this warning
could
result
in personal
iniury,
or death.
Never
operate
a furnace without
a filter or with filter access
door removed.
There
are
no provisions
for
an internal
filter
rack
in these
furnaces.
A
field-supplied,
accessory
external
filter
rack
is
required.
Refer to the instructions
supplied
with the external
filter rack for
assembly
and installation
options.
AIR DUCTS
General
Requirements
The duct
system
should
be
designed
and sized
according
to
accepted
national
standards
such
as those
published
by:
Air
Conditioning
Contractors
Association
(ACCA),
Sheet
Metal and
Air Conditioning
Contractors
National
Association
(SMACNA)
or
American
Society
of
Heating,
Refrigerating
and
Air
Conditioning
Engineers
(ASHRAE)
or consult
The Air Systems
Design
Guidelines
reference
tables
available
from
your
local
distributor.
The
duct
system
should
be
sized
to
handle
the
required
system
design
CFM at the design external
static pressure.
The furnace
airflow
rates are provided
in Table 5-Air
Delivery
CFM (With Filter).
When
a furnace
is installed
so that
the supply
ducts
carry
air
circulated
by the furnace
to areas outside
the space containing
the
furnace,
the return
air shall also be handled
by duct(s)
sealed
to
the furnace
casing
and ternfinating
outside
the space
containing
the furnace.
Secure ductwork
with proper
fasteners
for type of ductwork
used.
Seal supply-
and return-duct
connections
to furnace
with code
approved
tape or duct sealer.
NOTE:
Flexible
connections
should be used between
ductwork
and furnace
to prevent
transnfission
of vibration.
Ductwork
passing
through
unconditioned
space
should
be
insulated
to enhance
system
performance.
When
air conditioning
is used, a vapor barrier is recommended.
Maintain
a 1-in.
(25 ram)
clearance
from combustible
materials
to supply
air ductwork
for
a distance
of 36
in. (914
ram)
horizontally
from
the furnace.
See NFPA 90B or local
code for
further requirements.
Ductwork
Acoustical
Treatment
NOTE:
Metal duct systems
that do not have a 90 ° elbow
and 10
ft. (3 M) of main
duct to the first branch
take-off
may require
internal
acoustical
lining. As an alternative, fibrous ductwork
may
be used if constructed
and installed
in accordance
with the latest
edition
of SMACNA
construction
standard
on
fibrous
glass
ducts.
Both
acoustical
lining
and fibrous
ductwork
shall comply
with NFPA 90B as tested by UL Standard
181 for Class 1 Rigid
air ducts.
Supply
Air Connections
For a furnace
not equipped
with
a cooling
coil, the outlet duct
shall be provided
with
a removable
access
panel.
This opening
shall be accessible
when
the furnace
is installed
and shall be of
such a size that the heat exchanger
can be viewed
for possible
openings
using
light assistance
or a probe
can be inserted
for
sampling
the air stream.
The cover attachment shall prevent
leaks.
Upflow
and Horizontal
Furnaces
Connect
supply-air
duct to flanges
on furnace
supply-air
outlet.
Bend flange
upward
to 90 ° with wide
duct pliers. (See Fig. 14.)
The supply-air
duct must
be connected
to ONLY
the furnace
supply-outlet-air
duct
flanges
or air conditioning
coil
casing
(when
used).
DO NOT
cut main
furnace
casing
side to attach
supply
air duct, hunfidifier,
or other
accessories.
All accessories
MUST
be connected
to duct external
to furnace main casing.
NOTE:
For horizontal
applications,
the top-most
flange
may be
bent past 90 ° to allow the evaporator
coil to hang
on the flange
temporarily
while
the remaining
attachment
and sealing
of the
coil are performed.
15

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents