ABB Relion RES670 Product Manual page 59

Phasor measurement unit (pmu)
Hide thumbs Also See for Relion RES670:
Table of Contents

Advertisement

Phasor measurement unit RES670 2.1 IEC
Logic
Table 42. Tripping logic common 3-phase output SMPPTRC
Function
Trip action
Minimum trip pulse length
3-pole trip delay
Evolving fault delay
Table 43. Number of SMPPTRC instances
Function
SMPPTRC
Table 44. Number of TMAGAPC instances
Function
TMAGAPC
Table 45. Number of ALMCALH instances
Function
ALMCALH
Table 46. Number of WRNCALH instances
Function
WRNCALH
Table 47. Number of INDCALH instances
Function
INDCALH
Table 48. Number of AND instances
Logic block
AND
ABB
M12380-1 v9
Range or value
3-ph, 1/3-ph, 1/2/3-ph
(0.000-60.000) s
(0.020-0.500) s
(0.000-60.000) s
3 ms
6
GUID-3AB1EE95-51BF-4CC4-99BD-F4ECDAACB75A v1
3 ms
6
GUID-A05AF26F-DC98-4E62-B96B-E75D19F20767 v1
3 ms
-
GUID-70B7357D-F467-4CF5-9F73-641A82D334F5 v1
3 ms
-
GUID-EAA43288-01A5-49CF-BF5B-9ABF6DC27D85 v1
3 ms
-
GUID-D1179280-1D99-4A66-91AC-B7343DBA9F23 v1
3 ms
60
Accuracy
-
±0.2% or ±15 ms whichever is greater
±0.2% or ±15 ms whichever is greater
±0.2% or ±15 ms whichever is greater
Quantity with cycle time
8 ms
-
Quantity with cycle time
8 ms
6
Quantity with cycle time
8 ms
-
Quantity with cycle time
8 ms
-
Quantity with cycle time
8 ms
5
Quantity with cycle time
8 ms
60
1MRK 511 367-BEN D
100 ms
-
100 ms
-
100 ms
5
100 ms
5
100 ms
-
100 ms
160
59