5.2

OpenPCS 7 without OS

OpenPCS 7 station without installed OS client
In this configuration, the OpenPCS 7 station is installed without an OS client. The OPC clients
run on a separate PC. All OPC clients access the OpenPCS 7 station. The OpenPCS 7 station
contains the OPC DA, OPC HDA and OPC A&E servers.
This configuration is intended for large plants.
PCS 7 OS clients
PCS 7 OS server
S7-400
ET 200
Construct redundant connections for OpenPCS 7 stations in PCS 7
No redundant OpenPCS 7 station is implemented in PCS 7.
You can create redundancy of sorts by running several identical OpenPCS 7 stations. This
requires that your OPC client has the following functionality:
● Determination of the OpenPCS 7 station through which the necessary information is
● Detection of failure of an OpenPCS 7 station and failover to an available OpenPCS 7
OpenPCS 7