Product Description - Buderus Logamatic LON-Gateway Technical Information

Interface with ddc
Table of Contents

Advertisement

Product description

2.3 Product description
The Logamatic LON-Gateway is incorporated into a LON network via a twisted pair cable (twisted
2-wire line). The twisted pair cable is protected against reverse polarity.
Defined data of the Buderus control panel is implemented with the Logamatic LON-Gateway
interface on standard network variable types (SNVTs) for the LON data bus. The communication
includes forwarding of error messages, operating messages, and actual values, as well as changing
of set points and operating modes for boilers and consumers.
Fig. 1
Block diagram
1
Superior control system (building control system)
2
LON Gateway
Making the electrical connections
Connection of the Logamatic LON-Gateway
with Logamatic 4000
Connection of Logamatic LON-Gateway to
LON networks
Maximum cable length for FTT 10 depending
on the cable types used (see Echelon docu-
mentation).
Tab. 2
Electrical connections on the LON-Gateway
Technical Information Logamatic LON-Gateway - Subject to modifications resulting from technical improvements!
Logamatic LON-Gateway
ECOCAN-BUS interface (BUS communication),
3000 ft (1000 m) shielded cable
FTT-10A transceiver for incorporation via 2-wire cable
(twisted pair) to standardized LON BUS network; line or
free BUS topology possible
JY(ST)Y 2x2x0,8: max. 1050 ft (320 m) for node to node,
1640 ft (500 m) total
Cat5: max. 820 ft (250 m) for node to node 1480 t (450 m)
2
7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents