Boiler 2 - Buderus Logamatic LON-Gateway Technical Information

Interface with ddc
Table of Contents

Advertisement

Network interface

3.4.6 Boiler 2

This section describes "boiler 2." For boilers 3 and 4, the details apply accordingly.
38
Status burner boiler 2
Tab. 86 Indicator for boiler with Logamatic EMS or 4000
Burner OFF [0 %]
ON [> 0 %]
Current output [%]
39
Temperature boiler 2 (FK) actual
Tab. 87 Display of the current boiler temperature for boiler with Logamatic EMS or 4000
Note:
230 °F (110 °C) is an invalid value (e.g. no temperature sensor connected, sensor defective, etc.).
40
Boiler hours of operation 4000
boiler 2 level 1
Tab. 88 Display of the hours of operation for the level 1 (basic load) of boiler with Logamatic
4000 and third party burner
41
Boiler hours of operation 4000
boiler 2 level 2
Tab. 89 Display of the hours of operation for the modulation/level 2 (large load) of boiler with
Logamatic 4000 and third party burner
42
Pump 4000 boiler 2
Tab. 90 Operating message for the boiler circulation pump of the boiler with Logamatic 4000 and
third party burner
Pump OFF [0 %]
ON [> 0 %]
Current output [%]
43
Burner hours of operation EMS
boiler 2
Tab. 91 Display of the hours of operation for boiler with Logamatic EMS
Technical Information Logamatic LON-Gateway - Subject to modifications resulting from technical improvements!
SNVT_lev_cont (21)
SNVT_temp_p(105)
SNVT_time_hour(124) nvoKS2Br4000S1_h 2
SNVT_time_hour(124) nvoKS2Br4000S2_h 2
SNVT_lev_cont (21)
SNVT_time_hour(124) nvoKS1Br_EMS_h
nvoKS2_BrStatus
nvoKS2VLIst_Tp
nvoKS2PU_4000
3
1
2
1
2
35