Floor-Standing Boilers - Buderus Logamatic LON-Gateway Technical Information

Interface with ddc
Table of Contents

Advertisement

Network interface
Note:
230 °F (110 °C) is an invalid value (e.g. no temperature sensor connected, sensor defective, etc.).

3.2.5 Floor-standing boilers

This section describes "floor-standing boiler 1."
For boiler 2, the details apply accordingly.
47
Status burner boiler 1
Tab. 34 Display of the current burner level in operation and/or display of the current boiler output
for boilers with Logamatic EMS
High byte
OFF
xxxx xxxx
ON
xxxx xxxx
Tab. 35
x = the bit is not used
Boiler with Logamatic EMS boiler output
Example:
Factor
1
Display
x
Tab. 36
Result: 64 + 32 + 4 = 100% (only evaluate second byte)
X - is not used
49
Boiler supply temperature (FK) actual
Tab. 37 Display of the currently-measured supply temperature for a floor-standing multi-boiler
system
Note:
230 °F (110 °C) is an invalid value (e.g. no temperature sensor connected, sensor defective, etc.).
Technical Information Logamatic LON-Gateway - Subject to modifications resulting from technical improvements!
Boiler with Logamatic 4000
Burner 1st level on
Low byte
0xxx xxxx
1xxx xxxx
First byte
2
4
8
16
x
x
x
x
SNVT_state(83)
Burner 2nd level on / modulating
High byte
xxxx xxxx
xxxx xxxx
32
64
128
1
x
x
x
0
SNVT_temp_p(105)
nvoKS1Br1Stufe1
Low byte
x0xx xxxx
x1xx xxxx
Second byte
2
4
8
16
0
1
0
0
nvoKS1VLIst_Tp
3
2
32
64
128
1
1
0
2
21