MCAC-TSM-2008-02
2. Er01
High pressure>4.4MPa, display Er01, compressor and outdoor fan stop, the chiller can only resume
from protection manually.
Refer to the instruction manual: High pressure protection
Judge 1: check the high pressure switch is well.
Judge 2: Whether the temperature of external and inlet water is high
Check the operation conditions:
1.
the temperature of inlet water (cooling: below 20 ,
heating: below 45 )
2.
cooling: the indoor temperature is ≥17
ambient temperature is 10℃~43℃
3.
heating: the indoor temperature is ≤30
outdoor temperature is -15℃~24℃
Judge 3: Whether the refrigerant charge is excessive.
Check the temperature of compressor discharge and suction and
the pressure of compressor discharge and suction are normal.
Judge 4: Whether the air flow and water flow
are insufficient
Outdoor units
Values display indication Er01
Yes
Yes
Yes
Yes
Judge 5: PCB is malfunction.
Replace PCB
No
Replace the high pressure switch
No
and the
and the
No
Cooling: Check whether the speed of the fan
are normal. Heating: Check whether the water flow
volume can reach the data as follow :
Capacity
Water flow
volume (m
( kW)
5
0.86
7
1.24
9
1.54
10
1.74
Change the fan or pump.
Outdoor units
Stop the operation, and run it
at the normal condition.
Reclaim part of refrigerant
Capacity
Water flow
3
/h)
volume (m
( kW)
10
1.72
12
2.0
14
2.4
16
2.8
No
3
/h)
53